共查询到20条相似文献,搜索用时 15 毫秒
1.
Toshiyuki Sugimoto Yoshio Higashiyama Kazutoshi Asano 《Electrical Engineering in Japan》1998,122(4):1-7
The discharge occurring in a space-charge cloud was investigated by using a cloud of charged droplets. To produce a charged cloud with a definite space charge density and to cause a reproducible discharge, droplets ejected from an airless nozzle were induction charged and transported by air flow. The transportation of charged droplets by air flow was found to be quite effective in increasing the charge on the droplets and the charge density. Corona discharge was observed at a grounded needle electrode inserted into a charged droplet cloud with a charge density not exceeding 13 μC/m3. In negatively charged droplets, positive streamer coronas occurred. As the charge density of the cloud increased, the time interval of streamer pulses decreased and the discharge shifted to a glow corona. In positively charged droplets, the height and frequency of negative corona pulses increased with the charge density and the velocity of the charged droplet cloud. © 1998 Scripta Technica. Electr Eng Jpn, 122(4): 1–7, 1998 相似文献
2.
3.
4.
5.
Tetsuji Nishikawa Naoki Sakamoto Hideki Ueno Hiroshi Nakayama 《Electrical Engineering in Japan》2004,146(2):27-36
Discharge characteristics have been investigated for a needle–plane electrode configuration containing insulating barriers with a narrow gap which has been placed between the needle and the plane. The characteristics of creeping discharge developed in the narrow gap of the barrier filled with SF6 are especially considered. In the case of a configuration with a backside electrode below the needle, the corona generated from the needle easily extended to the gap. On the other hand, for a configuration without a backside electrode, the corona has hardly extended to the gap, and on increasing the applied voltage the corona developed greatly in the gap. This difference in corona extension should affect the flashover characteristics in the present system. © 2003 Wiley Periodicals, Inc. Electr Eng Jpn, 146(2): 27–36, 2004; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.10248 相似文献
6.
7.
电化学研究和蓄电池测试中常要用参比电极.在硫酸体系和铅酸蓄电池有关的研究中,常用硫酸亚汞(Hg/Hg2SO4)电极和镉电极作参比电极.前者常用于实验室的准确测量,它的缺点是价高、易碎和易造成环境污染.镉电极使用方便,但准确度较差.本文介绍硫酸银(Ag/Ag2SO4)参比电极的性能、制备及其在铅酸蓄电池中的实际应用.虽然Ag2SO4的溶解度较高,Ag+离子可能会污染电解液,采用合适的隔膜材料,可阻挡Ag+离子扩散污染,可以制成实用的硫酸银参比电极.硫酸银电极的电位比同溶液的硫酸亚汞电极要正0.038 4 V.硫酸银电极安全无毒(无汞、无镉)、使用方便、电位稳定和准确度高,可在硫酸盐体系的电化学研究和铅酸蓄电池的测试中广为应用. 相似文献
8.
9.
10.
回顾了近十年来国内外电子式电度表应用的情况,着重分析了国产单相电子式电度表的发展,指出电子式电度表的的优势和保证质量的关键因素,并展望了今后的发展。 相似文献
11.
开关柜内局部放电是引发开关柜绝缘故障的主要原因,局部放电检测能有效检测开关柜内局部放电缺陷,但暂态地电压法、超声波法及特高频检测方法受开关柜内本体结构及检测特征量影响,存在受干扰影响大且信号传输路径受限问题。本文研究开关柜高频脉冲电流局部放电检测方法,依据开关柜带电指示器结构设计微型高频传感器,建立开关柜不同类型局部放电检测方法对比平台,试验对比结果表明开关柜带电指示器引出线上采用高频脉冲电流法检测局部放电相对其他方法具有较高的灵敏度,开关柜高频脉冲电流法局部放电带电检测方法能够有效检测开关柜内不同类型的局部放电信号。 相似文献
12.
对网络流优化及其应用进行了研究,给出了不定向传输网络的优化数学模型及优化方法,编制了优化程序,并用来对IEEE六点节网络进行优化计算,计算结果令人满意。该优化方法及程序具有算法简单、计算速度快、占用计算机内存少的特点。 相似文献
13.
14.
随着新投运变电站或变电站扩建工程的增加,现场电流互感器二次极性检测任务繁重,目前较多使用的传统干电池点极性方法,不仅费时耗力,还容易出错。设计并研制一套电流互感器二次极性快速检测装置,介绍了该成果的理论依据和工作原理。通过在变电站工作现场的实际应用效果,验证了该装置的正确性和快速性。 相似文献
15.
APFC技术中的平均电流型控制及其应用研究 总被引:2,自引:0,他引:2
分析了有源功率因数校正 (APFC)技术中的平均电流型控制原理及其特点。用平均电流型控制原理设计一个APFC电路 ,并进行了实际测试 ,证明该平均电流型控制的优越性 相似文献
16.
讨论保护用电流互感器的暂态饱和及工程应用中的问题。互感器暂态饱和对保护装置性能有严重影响 ,为保证继电保护在暂态饱和条件下正确动作 ,工程应用中应合理选用电流互感器的类型和参数 ,保护装置必要时应采取减缓互感器饱和影响的措施。文中还列举大型发电机变压器组差动保护用电流互感器的选择计算示例 相似文献
17.
18.
讨论保护用电流互感器的暂态饱和及工程应用中的问题.互感器暂态饱和对保护装置性能有严重影响,为保证继电保护在暂态饱和条件下正确动作,工程应用中应合理选用电流互感器的类型和参数,保护装置必要时应采取减缓互感器饱和影响的措施.文中还列举大型发电机变压器组差动保护用电流互感器的选择计算示例. 相似文献
19.
变压器励磁涌流的特性分析及应用 总被引:10,自引:0,他引:10
由于变压器励磁涌流的存在,使得变压器差动保护有别于其他主设备及线路的差动保护。在现场工作的许多继电保护技术人员往往对变压器励磁涌流的机理概念模糊,造成其定值整定缺乏理论指导,往往凭经验给定。分析了变压器励磁涌流产生的机理,并给出了简洁明了的计算方法。 相似文献