1.
A CFD model of the 4th Beijing subway line was used to study the effect of longitudinal ventilation on heat and smoke plume movement in the tunnel. The critical ventilation velocity is correlated with the heat release rate for both a simplified heat fire source model and a complete combustion fire source model with methane gas as fuel. The influences of the heat source length and the fuel gas inlet geometry on the critical velocity are investigated for both fire source models. The results show that the influences of the combustion process and fire source area variation are not included in models based on Froude number preservation theory. Thus, Ri is no longer suitable as a dimensionless number for the critical ventilation velocity when the fire geometry or combustion conditions influence the results. The back-layering air temperature above the front of the fire source can be used to explain the different critical velocity variation regimes for all the simulation conditions.  相似文献   

2.
Critical velocity and smoke back-layering length are two of the determining parameters to the fire risk assessment of subway tunnel. These two parameters of a sloping subway tunnel with train blockage were investigated both experimentally and numerically in this paper. To address the influences of slope, the slopes of 0, 3, 6, 9, 12, 15% in downhill subway tunnel were studied and the height (H) of the tunnel was replaced by the inclined tunnel height (\( H/\cos \theta \)). The train model with a dimension of 2 m (length) × 0.3 m (width) × 0.38 m (height) was also chosen in simulations and experiments for the tunnel blockage. Thenceforward, 30 reduced-scale experimental and 150 numerical scenarios were analyzed to predict the critical velocity and smoke back-layering length in various sloping subway tunnels. Six different heat release rates including 5.58, 11.17, 16.67, 22.35, 27.94, and 33.52 kW were considered in the experiments and five different heat release rates including 2.79, 5.58, 8.38, 11.17 and 16.67 kW were considered in the simulations. Based on the comparison in the horizontal tunnel, numerical results were quite consistent with the experiments. The results showed that train blockage influenced the smoke back-layering length, and the critical velocity increases with the tunnel slope. Finally, empirical models were developed to predict the critical velocity and smoke back-layering length in a sloping subway tunnel with train blockage.  相似文献   

3.
Results from a series of fire tests carried out in a horizontal model tunnel (1:10) with longitudinal ventilation are presented. Pool fire with methanol as the fuel was used to simulate the fire source. Temperature and velocity distribution in the model tunnel were measured. The heat release rate, maximum gas temperature under the ceiling, back-layering length and critical velocity were investigated and compared with models proposed previously. Predicted maximum gas temperature under tunnel ceiling by Kurioka’s model agreed well with the experimental data with maximum discrepancy less than 20%. Dimensionless back-layering length was found decreased with the increase of the dimensionless ventilation velocity nearly linearly. Due to the difference between the experimental conditions and validating conditions of models proposed previously, diversities were found between the experimental results and predicted values base on Froude modeling. Maximum discrepancy on critical velocity might be about 40%. Models considering the effect of boundaries and heat loss of smoke more detailedly remain to be further developed.  相似文献   

4.
中国逐渐发展成为世界上隧道和地下工程最多的国 家,其长隧道数量和长度跻身世界前列。据统计,火灾中85%的 人员死亡是由热烟气造成的,目前隧道中采用较为广泛的排烟系 统有纵向排烟系统、集中排烟系统和横向排烟系统,而针对长隧道 来说,我国广泛采用的是竖井式纵向通风,因此,研究纵向通风与 竖井排烟综合效应下隧道火灾烟气流动特性及温度分布规律具有 重要意义。本文建立了1:10 缩尺寸竖井隧道模型,主隧道长度 16.5 m,宽度1.3 m,高度0.65 m;竖井通过排烟横通道与主隧道 连接,排烟横通道设置在主隧道侧面中部,尺寸为1.2 m 长、0.6 m 宽、0.4 m 高;竖井横截面为半径0.6 m 的1/4 圆,高4.6 m。在 竖井隧道模型中开展了一系列油池火实验,选取2 种方形燃烧池 (20 cm×20 cm、23 cm×23 cm)作为火源,设置2 个纵向火源位置 (位置A:火源中心线与排烟横通道中心线距离0.375 m;位置B: 火源中心线与排烟横通道中心线距离1.375 m),7 种纵向通风风 速(0,0.18,0.27,0.35,0.44,0.52,0.69 m/s),定量分析不同工 况下温度分布及烟气逆流长度。研究结果表明:当无纵向通风时, 火焰与隧道地板垂直,且呈轴对称形态;当有纵向通风时,火焰向 下游偏移,且纵向通风风速越大,火焰向下游偏移越明显;当纵向 通风风速为0 m/s 时,由于竖井的存在,火源上、下游两侧烟气温 度分布并非对称,火源下游(竖井侧)烟气温度下降速度较快,与单 洞隧道烟气温度分布明显不同;随纵向通风风速增加,烟气逆流长 度和烟气温度减小,而最大温度偏移距离整体呈增加趋势;当无量 纲纵向通风风速v′<0.19 时,主隧道最大温升△Tmax 与Q2/3/ Hef 5/3 呈正比,而当无量纲纵向通风风速v′>0.19 时,主隧道最大 温升△Tmax 与Q? /(vb1/3Hef 5/3)呈正比,但常数系数均小于Li 等预 测模型中的常数系数;竖井隧道内无量纲纵向烟气温度分布符合 Fan 和Ji 等建立的纵向温度衰减模型,衰减系数k′在1.36~1.63 范围内变化,但其值明显大于单洞隧道纵向温度衰减系数k′;另 外,当火源位于位置A 时,最大烟气温度低于火源位于位置B 时 的最大烟气温度,无量纲纵向烟气温度衰减速度慢于火源位于位 置B 时衰减速度。  相似文献   

5.
This paper investigates the buoyancy-driven smoke flow layering length (both upstream and downstream) beneath the ceiling with combination of point extraction and longitudinal ventilation in tunnel fires. A theoretical model is developed based on previous back-laying model with only longitudinal ventilation, with modified actual heat release rate, as well as modified upstream and downstream opposing longitudinal air flow velocities by the induced flow velocity due to point extraction. Experiments are carried out in a reduced scale model tunnel with dimensionless of 72 m×1.5 m×1.3 m. A LPG porous gas burner is used as fire source. The smoke flow layering length both upstream and downstream are identified based on temperature profiles measured along the ceiling, for different experiment conditions. CFD simulations with FDS are also performed for the same scenarios. Results show that with combination of point extraction and longitudinal ventilation, the smoke flow layering length is not symmetric where it is longer downstream than that upstream. The upstream smoke layering length decreases, while the downstream layering length increases with increase in longitudinal ventilation velocity; and they both decrease with increase in point extraction velocity. The predictions by the proposed theoretical model agree well with the measurements and simulation results.  相似文献   

6.
Curved tunnels are inevitable subjected to the city underground geological conditions. Due to the catastrophic consequence of tunnel fires with high population density, the related researches on fire safety of curved tunnel are full of significance. Therefore, a series of curved subway tunnels with turning radius of 300–1000 m were investigated numerically by FDS 5.5.3 in terms of the smoke back-layering length and critical ventilation velocity under the heat release rate of 5–10 MW. Theoretical analysis shows that the curved tunnel with the local resistance has an advantage of preventing smoke spreading compared with straight tunnel. The simulation results also indicated that both the smoke back-layering length and the critical ventilation velocity increased with the rising turning radius, and the straight tunnel has the largest values. In fact, the local resistance impact factor for the smoke back-layering length in the curved tunnel, \( k_{f} \), was controlled by turning radius \( R \) and ventilation velocity \( V \). The dimensionless critical velocity increased slightly from \( 0.638Q^{*1/3} \) to \( 0.669Q^{*1/3} \) when the turning radius increased from 300 m to 1000 m. Without considering the influence of turning radius (local resistance), previous models cannot be applied to the curved tunnel. The improved prediction models about smoke back-layering length and critical velocity with the factor of turning radius could provide a technical guideline for the tunnel ventilation designs.  相似文献   

7.
在真实地铁隧道内开展热烟试验,验证 FDS 模拟结果的正确性。建立地铁隧道三维物理模型,采用 FDS 研究室外空气设计参数对隧道火灾烟气返流长度和临界风速的影响。研究结果表明,室外空气设计参数对烟气返流长度和临界风速有较大的影响。室外空气温度越低,地铁隧道火灾烟气返流长度越长。 室外空气湿度越大,地铁隧道火灾烟气返流长度越短。室外大气压力越大,地铁隧道火灾烟气返流长度越短。  相似文献   

8.
In order to detect a fire and provide adequate fire protection to a tunnel structure, the maximum gas temperature beneath the ceiling to which the structure is exposed needs to be estimated. Theoretical analysis of maximum gas temperature beneath a tunnel ceiling based on a plume theory is given. The heat release rate, longitudinal ventilation velocity and tunnel geometry are taken into account. Two series of model-scale experimental tests were also carried out. The results of both analysis and experiments show that the maximum excess gas temperature beneath the ceiling can be divided into two regions. When the dimensionless ventilation velocity is greater than 0.19, the maximum excess gas temperature beneath the tunnel ceiling increases linearly with the heat release rate and decreases linearly with the longitudinal ventilation velocity. When the dimensionless ventilation velocity is less than 0.19, the maximum excess gas temperature beneath the ceiling varies as the two-thirds power of the dimensionless heat release rate, independent of the longitudinal ventilation velocity. In both regions, the maximum excess gas temperature varies as the −5/3 power of the vertical distance between the fire source bottom and tunnel ceiling. The investigation presented here considers only the cases when the continuous flame region is lower than the ceiling height.  相似文献   

9.
临界风速可有效控制烟气蔓延,是隧道防灾通风重要参数。为分析隧道长度对临界风速的影响,采用量纲分析法构建临界风速与隧道长度关系公式,并分别在5 MW和30 MW火源热释放速率下,对不同长度隧道的火灾进行数值模拟以量化研究隧道长度对临界风速的影响。结果表明,隧道长度对临界风速具有影响,且不同火源释放速率时影响也有所不同:无量纲火源热释放速率小于0.15时,临界风速随隧道长度增大呈现1/41次方增长关系;无量纲火源热释放速率高于0.15时,临界风速随隧道长度增大呈现1/25次方增长关系。进而建立了考虑隧道长度的无量纲临界风速计算公式。  相似文献   

10.
利用PHOENICS模拟了两种纵向风速下隧道内火灾烟气的发展情况,分析了人员疏散方向离火源点不同距离处烟气的温度和浓度分布。提出了利用联络通道来疏散部分人群的方法,得出了使联络通道内无烟的纵向通风速度,为提出全面的地铁区问隧道火灾人员疏散模式提供有益参考。  相似文献   

11.
隧道火灾是运营公路隧道的主要灾害。为有效控制隧道火灾,采用理论分析和数值模拟相结合的方法研究了设排烟道隧道的火灾烟气逆流长度与临界风速。以国内常见的双车道隧道尺寸建立模型,分析了排烟速率和纵向通风速率对烟气逆流长度的影响,提出了临界风速的预测模型。并将其通风效果与常规未设排烟道的纵向通风做了比较。结果表明:未设排烟道时,纵向风速还未达到临界风速时,火灾下游烟气的层化状态就已破坏。设排烟道能及时排出火灾产生的烟气,有利于保持烟气的层化状态,有效改善火灾时的隧道环境,为火灾下游人员的疏散救援提供了有利条件。同时,设置排烟道有利于减小逆流长度和临界风速。随着排烟速率的增大,相应的临界风速呈指数函数递减的特性。  相似文献   

12.
临界风速的研究对于隧道火灾时的烟气控制、消防救援、人员逃生等有重要意义。临界风速的计算受到火源和洞内车辆阻滞的影响,为了给出考虑上述阻塞的临界风速计算公式,建立了考虑隧道火灾时火源和洞内车辆阻塞数值计算模型,分析了火源处阻塞或上游车辆阻塞单一因素对临界风速的影响;修正了考虑火源处阻塞的临界风速计算公式;提出了一个新的同时考虑火源上游阻塞以及火源断面阻塞的无量纲临界风速计算公式,并与实验结果进行对比验证其准确性。研究表明:本文公式平均误差在10%以内,临界风速随阻塞比增大而减小,火源处阻塞对临界风速的影响显著于上游车辆阻塞。  相似文献   

13.
Twelve tests were conducted to study the distribution of smoke temperature along the tunnel ceiling in the one-dimensional spreading phase, two tests in a large-scale tunnel and the other ten in full scale vehicular tunnels. The fire size and the height above the floor, the tunnel section geometry and longitudinal ventilation velocity varied in these tests. Experimental results showed that when the fire size was larger, the smoke temperature below the ceiling was higher, but it decayed faster while traveling down the tunnel. The longitudinal ventilation velocity seemed to take much influence on the smoke temperature decay speed downstream. A “barrier effect” was shown for the smoke temperature distribution of the upstream back layering. The smoke temperatures measured were higher upstream than downstream before the “barrier”, and were much lower and decreased faster along the tunnel ceiling after the “barrier”. The temperature and the traveling velocity of the upstream smoke flow decreased largely when the longitudinal ventilation velocity increased a bit. The dimensionless excess smoke temperature distributions along the tunnel ceiling in all tests fell into good exponential decay. But the decay speed along the tunnel seemed to be much larger in the large-scale tunnel than that in full-scale tunnels. The measured data on ceiling jet temperature decay along the tunnel was compared with predictions of Delichatsios's model, a model built based on small-scale tests, with hydraulic diameter introduced. Results showed that Delichatsisos’ model over estimated the decay speed of ceiling jet temperature for the downstream flow. However, good agreement was achieved between the measured data and the model predictions for the upstream back layering. All the experimental data presented in this paper can be further applied for verification of numerical models, bench-scale results and building new models on ceiling jet temperature distribution.  相似文献   

14.
Results from a series of tests in a model tunnel (1:23) are presented. Tests were carried out with longitudinal ventilation under different fire conditions. Wood cribs were used to simulate the fire source, which was designed to correspond to a scaled-down HGV (Heavy Goods Vehicle) fire load. The parameters tested were: the number of wood cribs, type of wood cribs, the longitudinal ventilation rate and the ceiling height. The heat release rate, fire growth rate, maximum gas temperature beneath the ceiling, temperature distribution, total heat flux at floor level, flame length, and back-layering length were investigated. Correlations for these parameters were investigated and proposed for longitudinal flow in tunnels.  相似文献   

15.
通过对海拔为4100m的高海拔隧道进行全尺寸火灾试验,揭示高海拔隧道火灾烟气下沉及温度场变化特征。试验采用三种不同尺寸火源(0.8m2、1.0m2、2.0m2),对隧道火灾烟气蔓延特征、火区最高温度、隧道拱顶纵向温度分布进行研究。试验研究结果表明:隧道火灾试验初期及燃烧稳定阶段,火源附近隧道上层烟气与下层冷空气分界明显,火灾后期烟气下沉严重;较小风速有利于高海拔隧道小规模火灾烟气逆流层纵向和垂向蔓延的控制。隧道火灾温度场研究表明:隧道火灾温升速率随火源热释放率增大而增加;火源附近20m范围内温度衰减速率较快,远火源区域隧道拱顶纵向温度衰减较慢,趋于平缓;通过对火源上方拱顶烟气温度分析,发现隧道火灾探测采用差温报警模式较定温报警模式更加有效,并得出10℃/min的温升速率可基本满足高海拔隧道小规模火灾的初期报警;隧道拱顶纵向温度分布规律导致火源远场烟气下沉严重而近火源区域烟气层化较好的特征。高海拔隧道火灾温度分布特性试验研究,可为高海拔隧道火灾动力特性研究提供依据,为高海拔隧道人员疏散逃生提供指导及建议。  相似文献   

16.
In this work, a numerical model of tunnel fire is developed and aimed to investigate the influence of cross-sectional fire locations on critical velocity and smoke flow characteristic. It is shown that the critical velocity for a fire next to the wall is obviously higher than that for a fire in the middle or on the left/right lane. The ratio is estimated to be 1.12. The predictions of critical velocity from ‘small-fire’ models show a good agreement with that for a fire in the middle or on the left/right lane from CFD. The tunnel height at the fire location is proposed to be instead of the hydraulic tunnel height in the ‘big-fire’ model of Wu and Bakar for a fire next to the wall. The smoke moves backward in a tongue like form as the ventilation velocity is lower than the critical velocity. The back-layering length of a fire in the middle is shown to be approximate twice than that on the left/right lane under the same ventilation velocity, although they share the same critical velocity. Whereas a relatively short back-layering length for a fire next to the wall under the velocity of 2.6 and 2.7 m/s. In addition, a snaky high-temperature profile on the top wall at the initial downstream is observed for a fire on the left lane and next to the wall, and finally a steady and layered smoke flow. The likely cause of this phenomenon is subsequently explained in this study.  相似文献   

17.
基于数值模拟的方法,采用PyroSim 软件搭建半径分别为250、300、400、500、600 m 的曲线隧道模型及长度为130.8 m 的直线模型,模拟隧道火灾发生后无纵向通风时的烟气运动,对比分析两种模型中心线上不同高度的烟气温度。模拟分析得到:火灾前期,直线模型中烟气蔓延时基本关于隧道中心线对称,而曲线模型中烟气运动时在上游偏向凹壁下游偏向凸壁;达到稳定状态时,直线模型中火源正上方温度高于曲线模型,无论近火源区还是远火源区,直线模型温度纵向分布关于火源位置均具有很好的对称性,而曲线模型中表现为近火源区波动较大,远火源区温度衰减梯度大于直线模型,1.6 m 高度上游温度衰减梯度大于下游;提出曲线模型中顶棚温度纵向衰减指数模型。  相似文献   

18.
纵向通风目前是我国长隧道使用最多的通风排烟方式。通过1∶ 10隧道模型火灾排烟试验,利用激光片光观测火灾烟气分层结构,分析了纵向通风对火灾烟气分层结构的影响;通过数值模拟,研究了隧道采用纵向通风排烟的效果。结果表明:在无风情况下,火灾初期烟气能够较好地维持在隧道顶部,与空气分层界限明显;开启纵向排烟后,能够有效抑制火灾烟气向火源上游蔓延,但烟气分层结构遭到破坏并随着风速增加逐渐消失,火源下游区域能见度下降;纵向排烟风速维持在临界风速及以下,可降低纵向风对烟气分层的影响。  相似文献   

19.
摘 要:为了解决特长海底隧道发生火灾时的排烟问题,提出利用服务通道和联络横通道辅助送风的通风方案。利用火灾动力学模拟软件(FDS),建立隧道火灾通风模型,通过研究通风排烟时服务隧道内补风量与横通道开启数量对火灾烟气的控制效果,确定通风系统的技术参数。结果表明:火灾发生时,事故隧道内纵向通风风速2 m/s,同时开启火源上游3 个横通道,并在服务隧道两端各施加1.3 m/s 纵向通风风速,既可将烟气控制在火源一侧,同时不影响人员安全疏散,其控烟效果与通风网络解算结果一致。采用横通道辅助送风的通风方案,控制特长海底隧道内火灾烟气蔓延是具有理论可行性的。  相似文献   

20.
We examined the exhaust performance of a hybrid ventilation strategy for maintaining a safe evacuation environment for tunnel users in a tunnel fire. The hybrid ventilation strategy combines the longitudinal ventilation strategy with the point ventilation strategy which is a type of transverse ventilation strategy. The model tunnel developed by this study was scaled to 1/5 the size of a full-scale tunnel. The model-scale experiment was performed taking into consideration Froude's law of similarity. Measurement items were the distribution of temperature and concentration of smoke inside the tunnel, longitudinal wind velocity, mass flow of smoke in the point ventilation duct, and the heat release rate of the fire source. The following main conclusions were obtained. The smoke height was constant even when varying the extraction rate of smoke from the ceiling vent. The backlayering length and critical velocity of the smoke flow in the hybrid strategy could be predicted by the methodology developed by using the longitudinal strategy. The hybrid strategy maintained a safe evacuation environment on both sides of the tunnel fire.  相似文献   