首页 | 本学科首页   官方微博 | 高级检索  
相似文献
 共查询到20条相似文献,搜索用时 15 毫秒
1.
A new fault location method suitable for multi-terminal transmission lines that combines the advantages of both impedance and traveling wave based methods has been developed and presented in this paper. The proposed method first determines whether the fault is grounded or ungrounded by comparing the magnitude of the ground mode wavelet coefficients at the measurement end. Next, the impedance based method is used to identify the faulted half of the line in the case of two-terminal line and the faulted line section as well as the faulted half of the line section in the case of multi-terminal lines. Finally the fault location is determined by taking the time difference between the first two consecutive aerial modes of the current traveling waves observed at one end of the multi-terminal line. The proposed method has been tested on four- and five-terminal transmission lines with different types of faults, fault resistances and fault inception angles using ATP simulation.  相似文献   

2.
针对现有多端输电线路故障行波检测困难、定位精度不高、判定算法复杂等问题,提出一种基于变分模态分解(VMD)算法和Hilbert变换相结合的行波检测法和一种基于差值矩阵的多端输电线路故障行波定位算法。首先通过行波传感器采集故障行波信号,利用VMD分解算法对故障行波进行分解,结合Hilbert变换提取模态分量IMF1的瞬时频率,根据第一个瞬时频率的奇异点位置确定故障行波的达到时刻。然后利用行波到达各端的时间和行波传输原理,得到多端输电线路故障分支判定矩阵。最后根据故障分支判定矩阵确定故障支路,实现故障点的精确定位。ATP/EMTP仿真结果表明,所提检测方法能够准确检测故障初始行波的到达时间,多端输电线路定位算法能够准确判定故障支路,相比于HHT检测方法下的定位算法,进一步提高了定位精度。  相似文献   

3.
配电网多为树形结构,分支多,单端定位或双端定位方法都很难准确定位故障。针对B型行波和配电网树形结构,提出了一种多端行波故障定位方法。该方法利用接地故障时刻产生的行波第1波头到达配电网线路各末端的时刻进行故障定位。利用行波故障定位基础理论,建立了多端行波故障定位的理论依据,考查了定位方案在配电网中的优越性。采用ATP仿真软件和MATLAB软件对该方案在配电网中遇到的各种情况进行了仿真分析。仿真结果表明,在配电网单相接地故障定位中,多端行波定位法只利用接地故障初期很短时间内的暂态行波信号,接地故障后期的故障发展情况对开始的暂态行波信号并无影响,所以运用多端行波定位法能够快速准确地找到故障点。  相似文献   

4.
基于三点电流测量的输电线路行波故障定位新方法   总被引:6,自引:0,他引:6  
鉴于输电线路在线监测取得了长足的进步,针对目前行波定位法中波头检测算法存在缺陷和波速测定精度差的不足,本文提出了基于导线电流三测量点局域均值分解(LMD)的行波故障定位新方法。该方法首先对测量点电流线模分量进行局域均值分解,然后根据分解得到的第一个PF分量瞬时频率曲线的首个频率突变点来确定行波波头第一次到达测量点的时刻。其次,根据相位差动保护原理判断出故障点所在线路段,并利用无故障段线路的长度和故障行波到达其两端测点的时间差之比计算出故障行波波速。最后,通过双端行波法的定位原理计算出故障距离。仿真结果表明,本文定位方法同基于小波变换或希尔伯特-黄变换的定位方法相比具有较高的定位精度。  相似文献   

5.
Cloud computing technology is used in traveling wave fault location, which establishes a new technology platform for multi-terminal traveling wave fault location in complicated power systems. In this paper, multi-terminal traveling wave fault location network is developed, and massive data storage, management, and algorithm realization are implemented in the cloud computing platform. Based on network topology structure, the section connecting points for any lines and corresponding detection placement in the loop are determined first. The loop is divided into different sections, in which the shortest transmission path for any of the fault points is directly and uniquely obtained. In order to minimize the number of traveling wave acquisition unit (TWU), multi-objective optimal configuration model for TWU is then set up based on network full observability. Finally, according to the TWU distribution, fault section can be located by using temporal correlation, and the final fault location point can be precisely calculated by fusing all the times recorded in TWU. PSCAD/EMTDC simulation results show that the proposed method can quickly, accurately, and reliably locate the fault point under limited TWU with optimal placement.  相似文献   

6.
This paper presents a day-ahead optimal energy management strategy for economic operation of industrial microgrids with high-penetration renewables under both isolated and grid-connected operation modes. The approach is based on a regrouping particle swarm optimization (RegPSO) formulated over a day-ahead scheduling horizon with one hour time step, taking into account forecasted renewable energy generations and electrical load demands. Besides satisfying its local energy demands, the microgrid considered in this paper (a real industrial microgrid, “Goldwind Smart Microgrid System” in Beijing, China), participates in energy trading with the main grid; it can either sell power to the main grid or buy from the main grid. Performance objectives include minimization of fuel cost, operation and maintenance costs and energy purchasing expenses from the main grid, and maximization of financial profit from energy selling revenues to the main grid. Simulation results demonstrate the effectiveness of various aspects of the proposed strategy in different scenarios. To validate the performance of the proposed strategy, obtained results are compared to a genetic algorithm (GA) based reference energy management approach and confirmed that the RegPSO based strategy was able to find a global optimal solution in considerably less computation time than the GA based reference approach.  相似文献   

7.
一种新型的输电线路双端行波故障定位方法   总被引:8,自引:0,他引:8       下载免费PDF全文
针对行波故障测距技术中行波检测准确性和行波波速对测距精度的影响,提出一种新的双端行波故障定位方法。首先,介绍了变分模态分解(Variational Mode Decomposition,VMD)和 Teager能量算子(Teager Energy Operator,TEO)的特点,并将VMD与TEO相结合应用于故障行波波头的检测。其次,在双端行波故障测距原理的基础上,根据故障行波的传播路径,推导出一种不受行波波速和线路实际长度变化影响的行波故障测距新算法。该算法不需要检测行波反射波的波头,测距原理简单。最后,通过EMTDC仿真验证方法的正确性和准确性。大量的仿真结果表明该方法行波波头检测效果较好,测距准确度较高。  相似文献   

8.
分析了直流输电系统在单极运行方式下,接地极线路故障暂态行波和外部注入脉冲信号在接地极线路上的传播过程。以此为基础,提出一种将脉冲注入法和单端故障行波法相结合的接地极线路故障测距方案。首先通过在换流站直流中性母线处监测接地极线路故障暂态行波识别线路是否发生故障,在线路故障暂态过程结束后从中性母线向线路注入脉冲信号。根据脉冲注入法得到初步测距结果,并以此确定故障区段。然后,根据确定的故障区段,进一步用单端故障行波法再次获得测距结果。最后,对两次测距结果取平均值,作为最终测距结果。以PSCAD/EMTDC为仿真平台,搭建了直流输电系统在单极运行方式下的接地极线路故障测距仿真模型。并借助Matlab对仿真波形数据进行分析,表明所提出的接地极线路故障测距方案是可行的。  相似文献   

9.
通过分析多端柔性直流系统直流线路故障后故障电压行波的传播特点,利用能够同时检测信号突变时刻和突变极性的数学形态学滤波器,设计采用双端信号进行故障测距的方案。通过对行波波头间隔取均值,提高了在线路端口附近故障时的测距精度。利用估计的行波速度,确定行波波头的查找区间,提高了测距的抗干扰能力。该方法无需线路参数信息和两端数据同步,采样频率要求较低,抗噪声能力强。搭建了三端柔性直流系统进行仿真分析,仿真结果表明所提故障测距方案在各种情况下均可得到较高精度的测距结果。  相似文献   

10.
针对现有配电网故障定位方法存在实现复杂、可靠性不高的问题,提出一种基于多端行波时差的配电网故障定位方法.首先,分析故障行波传输特性,提出一种配电网故障状态表达式.根据多端行波时差和双端行波原理计算故障距离理论值.将理论值代入故障状态表达式,搭建故障搜索矩阵和辅助矩阵,通过分析矩阵元素变化特征和数值状态定位故障线路.然后...  相似文献   

11.
为解决复杂树型配电网长期存在的单相接地故障精确定位难题,分析了故障行波模量的传输特性,提出了一种基于两种行波原理组合的故障定位新方法。该方法首先建立多端定位算法查找故障主干线路,缩小故障定位范围;然后提出基于行波模量时差的双端定位算法,利用行波线模分量与零模分量的行波传输时差准确计算故障距离;最后,综合利用多端与双端定位结果确定故障精确位置。经仿真验证,该方法仅需在部分配电线路末端安装行波定位装置即可实现配电网全网线路的精确故障定位,有效节省了装置投资成本,具有数据处理量少、算法实现简单等优点。  相似文献   

12.
为降低海上风电场结构复杂、故障行波信号微弱等因素对集电线路故障定位的影响,提出一种基于决策系数与极点对称模态分解-Teager能量算子ESMD-TEO(extreme-point symmetric mode decomposition-Teager ener?gy operator)的集电多分支线路故障定位方法.分析...  相似文献   

13.
为了满足多端柔性直流电网输电线路超高速保护动作快速需求,在传统直流线路保护的基础上,介绍了柔性直流线路的保护配置和动作策略,根据故障行波的特征,提出了一种行波保护方法。该方法将电压信号经过S变换提取故障行波的特定频带特性,通过对不同时刻故障行波幅值的变化识别接地短路故障,进而构成行波保护出口的判据。最后基于实际工程参数,在RTDS搭建的多端柔性直流仿真模型与控制保护系统构成的闭环系统上进行试验验证,试验结果表明该方法有效、可靠。  相似文献   

14.
针对配电网网络结构复杂,分支多,故障定位困难,提出了一种单端、多端相结合的配电网单相接地故障行波定位方法。首先根据配电网拓扑结构,依据最优配置原则,选取需安装行波定位装置的配变终端,然后通过奇异值分解(SVD)对故障行波信号进行检测,应用多端行波故障选线算法判别障故障线路。在此基础上,各行波定位装置采用小波波形相关性方法,检测两个相关反射波时间差进行单端行波测距,并进行信息融合,得出最终定位结果。仿真结果表明,该方法在某台定位装置失灵、时间记录错误时也能实现配电网的故障准确定位,具有很强的容错性和较高的定位精度。  相似文献   

15.
为解决多端直流混合输电线路故障定位以及传统故障定位存在的波速影响的问题,本文对不同拓扑结构的线路提出定位方案。利用变分模态分解与Teager能量算子结合固有频率和行波时域定位确定了新型的定位方案,同时利用固有频率识别不同拓扑下的故障区域,并将Schavemaker电弧模型应用于弧光高阻故障影响分析中。PSCAD/EMTDC平台仿真结果表明,本文方案能准确定位不同区段的故障,综合的定位误差为+/-500 m。在方案稳定性分析中,结果表明在高阻、高噪声以及弧光高阻情况该方案仍能表现良好。最后,将本文方案与行波双端时域定位方案对比,本文方案可有效避免线路参数变化的影响。  相似文献   

16.
电力系统行波测距方法及其发展   总被引:5,自引:2,他引:5       下载免费PDF全文
行波测距法具有测距精度高、定位速度快的特点,目前主要应用在高压输电线路中。首先比较全面地讨论了行波测距算法及研究现状,根据行波测距算法的原理不同,将其分为基于单条输电线路的单端法、多端法和基于广域行波信息的网络测距法,重点对单端法中的反射波识别、双端法中的GPS和IEEE1588对时、广域网络测距法中的IEC61850标准等问题进行了探讨。然后回顾了行波的获取、波头的检测,波速对测距的影响及消除行波波速的测距算法等关键问题的最新研究进展。在此基础上总结了行波法测距今后急需解决的关键问题。相关研究结果表明,行波故障测距在电力系统中有广泛的应用前景,是今后输电线路故障定位领域的重要发展方向。  相似文献   

17.
针对传统行波保护在高压直流输电线路中耐受过渡电阻能力不足、T区两侧故障线路定位依赖边界元件等问题,以最具代表性的多端混合高压直流系统为例,从数学层面上分别明晰了高压直流输电线路区内外故障和T区故障下的行波特征,进而构造了不同采样周期下的时域暂态电压比判据,以削弱T区和过渡电阻的影响,实现区内外故障识别;利用时域电压比判据,提出了基于单端量保护配合的高压直流输电线路暂态保护方案,实现了高压直流输电线路故障的快速判别以及T区两侧故障线路的准确定位;最后,利用实际工程的电磁暂态仿真模型对所提方法进行详细验证,结果表明,所提保护方案可行且具有较高的灵敏性和可靠性。  相似文献   

18.
当线路末端故障时,行波在线路末端的反射情况比较复杂,反向电流行波的极性有可能与正向电流行渡的极性相反,而此时测距结果又与线路无故障时相同。因此,会造成行波蒯距式与行波极性比较式合闸保护的不正确动作。根据行波的折、反射理论,分析出当线路无故障时正向电流行渡仅在线路末端发生反射,且电流行波的反射系数为-1,而当线路存在故障时,正向电流行波将在故障点发生反射,无论故障是否在线路末端,电流行波的反射系数都不会是-1。根据这一特征,提出了一种新的行波合闸保护方法。从原理上保证了在各种情况下保护都可以正确动作,大量的电磁暂态仿真结果也证明了这一点。  相似文献   

19.
针对现存多终端直流传输(MTDC)系统灵活性差和可靠性低的问题,提出一种新的基于行波系统故障定位方法,利用小波变换和同步电流测量来确定故障位置。首先通过排除不可能为故障的线路来区分故障区段,然后提出一种评估指标,以确定故障区段所包含的所有线路中的故障线路,最后构建并求解故障开始时间、故障位置和首次到达各个检测器时间的线性方程组。仿真结果表明,具有高精度、噪声免疫和故障阻抗鲁棒性,其中高阻抗鲁棒性是最大优势。  相似文献   

20.
为解决配电网行波波头检测困难的问题,提出一种基于随机共振-变分模态分解(SR-VMD)的行波信号检测方法.利用粒子群优化的变尺度SR对行波信号进行预处理,有效提高输出信号的信噪比.利用VMD算法将输出信号进行自适应分解,应用到故障定位中.用Teager能量算子(TEO)对行波波头进行标定,代入测距公式得到故障距离.仿真...  相似文献   