The main purpose of this study is to investigate the performance of an autocascade refrigeration system using zeotropic refrigerant mixtures of R744/134a and R744/290. One of the advantages of this system is the possibility of keeping the highest pressure of the system within a limit by selecting the composition of a refrigerant mixture as compared to that in the vapor compression system using pure carbon dioxide. Performance test and simulation have been carried out for an autocascade refrigeration system by varying secondary fluid temperatures at evaporator and condenser inlets. Variations of mass flow rate of refrigerant, compressor power, refrigeration capacity, and coefficient of performance (COP) with respect to the mass fraction of R744 in R744/134a and R744/290 mixtures are presented at different operating conditions. Experimental results show similar trends with those from the simulation. As the composition of R744 in the refrigerant mixture increases, cooling capacity is enhanced, but COP tends to decrease while the system pressure rises.
Résumé
The main purpose of this study is to investigate the performance of an autocascade refrigeration system using zeotropic refrigerant mixtures of R744/134a and R744/290. One of the advantages of this system is the possibility in keeping the highest pressure of the system within a limit by selecting the composition of a refrigerant mixture as compared to that in the vapor compression system using pure carbon dioxide. Performance test and simulation have been carried out for an autocascade refrigeration system by varying secondary fluid temperatures at evaporator and condenser inlets. Variations of mass flow rate of refrigerant, compressor power, refrigeration capacity, and coefficient of performance (COP) with respect to the mass fraction of R744 in R744/134a and R744/290 mixtures are presented at different operating conditions. Experimental results show similar trends with those from the simulation. As the composition of R744 in the refrigerant mixture increases, cooling capacity is enhanced, but COP tends to decrease while the system pressure rises. 相似文献
In the present study, two empirical correlations from the test results of 15 ejectors are derived for the performance prediction of ejectors using R141b as the working fluid. The ratio of the hypothetical throat area of the entrained flow to the nozzle throat area Ae/At, the geometric design parameter of the ejector A3/At, and the pressure ratios Pg/Pe and Pc*/Pe are used to correlate the performance of the ejector. The prediction of the entrainment ratio ω using the correlations is within ±10% error. A method of calculation for the ejector design using the correlations is also developed. R141b is shown in the present study to be a good working fluid for an ejector. The measured ω for the ejectors used in the present study can reach as high as 0.54 at Pg=0.465 MPa (84°C), Pc*=0.087 MPa (28°C) and Pe=0.040 MPa (8°C). For Pg=0.538 MPa (90°C), Pc*=0.101 MPa (32°C) and Pe=0.040 MPa (8°C), ω reaches 0.45.
Résumé
Dans cette étude, on a établi deux corrélations empiriques à partir des résultats expérimentaux obtenus utilisant 15 éjecteurs; ces corrélations ont été utilisées ensuite pour prédire la performance d'éjecteurs utilisant le R141b comme fluide frigorigène. Les rapports Ae/At (section de passage du fluide entraîné rapporté à la section théorique du col de l'éjecteur), et A3/At (section de sortie de l'éjecteur rapporté à la section théorique du col de l'éjecteur) et les relations entre pressions Pg/Pe et Pc*/Pe sont utilisés pour trouver la corrélation de la performance de l'éjecteur. La prévision du taux d'entraînement à partir des corrélations est précise à la hauteur de ±10%. Les auteurs ont également développé une méthode de calcul permettant de concevoir des éjecteurs à partir des corrélations. On a montré dans cette étude que le R141b s'avère être un fluide actif efficace pour cette utilisation. Le ω mesuré des éjecteurs utilisés dans cette étude peuvent atteindre 0.54 à Pg=0.465 MPa (84°C), Pc*=0.087 MPa (28°C) et Pe=0.040 MPa (8°C). Pour Pg=0.538 MPa (90°C), Pc*=0.101 MPa (32°C) et Pe=0.040 MPa (8°C), ω atteint 0.45. 相似文献
Flow condensation heat transfer coefficients (HTCs) of R22, R134a, R407C, and R410A inside horizontal plain and microfin tubes of 9.52 mm outside diameter and 1 m length were measured at the condensation temperature of 40 °C with mass fluxes of 100, 200, and 300 kg m−2 s−1 and a heat flux of 7.7–7.9 kW m−2. For a plain tube, HTCs of R134a and R410A were similar to those of R22 while HTCs of R407C are 11–15% lower than those of R22. For a microfin tube, HTCs of R134a were similar to those of R22 while HTCs of R407C and R410A were 23–53% and 10–21% lower than those of R22. For a plain tube, our correlation agreed well with the present data for all refrigerants exhibiting a mean deviation of 11.6%. Finally, HTCs of a microfin tube were 2–3 times higher than those of a plain tube and the heat transfer enhancement factor decreased as the mass flux increased for all refrigerants tested. 相似文献
A capillary tube is a common expansion device used in small sized refrigeration and air-conditioning systems. A generalized correlation for refrigerant flow rate in adiabatic capillary tubes is developed by implementing dimensionless parameters based on extensive experimental data for R-22, R-290, and R-407C measured in this study. Dimensionless parameters are derived from the Buckingham Pi theorem, considering the effects of tube inlet conditions, capillary tube geometry, and refrigerant properties on mass flow rate. The generalized correlation yields good agreement with the present data for R-22, R-290, and R-407C with average and standard deviations of 0.9 and 5.0%, respectively. Approximately 97% of the present data are correlated within a relative deviation of ±10%. Further assessments of the correlation are made by comparing the predictions with measured data for R-12, R-134a, R-152a, R-410A, and R-600a in the open literature. The correlation predicts the data for those five refrigerants with average and standard deviations of −0.73 and 6.16%, respectively. 相似文献
This paper outlines the framework of a semi-theoretical model for predicting the pool boiling heat transfer of refrigerant/lubricant mixtures on a roughened, horizontal, flat pool-boiling surface. The predictive model is based on the mechanisms involved in the formation of the lubricant excess layer that exists on the heat transfer surface. The lubricant accumulates on the surface in excess of the bulk concentration via preferential evaporation of the refrigerant from the bulk refrigerant/lubricant mixture. As a result, excess lubricant resides in a thin layer on the surface and influences the boiling performance, giving either an enhancement or degradation in heat transfer. A dimensionless excess layer parameter and a thermal boundary layer constant were derived and fitted to data in an attempt to generalize the model to other refrigerant/lubricant mixtures. The model inputs include transport and thermodynamic refrigerant properties and the lubricant composition, viscosity, and critical solution temperature with the refrigerant. The model predicts the boiling heat transfer coefficient of three different mixtures of R123 and lubricant to within ±10%. Comparisons of heat transfer predictions to measurements for 13 different refrigerant/lubricant mixtures were made, including two different refrigerants and three different lubricants. 相似文献
The option of using natural working fluids as a substitute of R-22 for solar-boosted heat pumps depends not only upon thermal performance and hazardous rating but also on potential impacts on the environment. This paper presents the comparative assessment of natural working fluids with R-22 in terms of their characteristics and thermophysical properties, and thermal performance. Some justification is given for using natural working fluids in a solar boosted heat pump water heater. The results show that R-744 is not suitable for solar-boosted heat pumps because of its low critical temperature and high operational pressures. On the other hand, R-717 seems to be a more appropriate substitute in terms of operational parameters and overall performance. However, major changes in the heat pumps are required. R-290 and R-1270 are identified as candidates for direct drop-in substitutes for R-22. 相似文献
Outside (refrigerant) boiling coefficients for a combination of spray and drip boiling for a low pressure refrigerant have been obtained from overall heat transfer coefficients in a 1024 fins per meter tube bundle segment. The tubes were heated by water on the inside; liquid refrigerant was sprayed and/or dripped on the outside. Also, refrigerant vapor was supplied at the bottom of the bundle segment. This configuration simulates an actual flooded evaporator under spray boiling conditions. The dripping corresponds to liquid film falling from upper rows while the inlet vapor is equivalent to the vaporized refrigerant rising from lower tubes; the refrigerant vapor can influence heat transfer performance by the combined effects of gas convection and liquid shear on the tubes. For a nominal heat flux of 23,975 W/m2, a bundle average outside heat transfer coefficient of 8522 W/m2 °C, based on nominal tube outer diameter, was found at an average bundle vapor mass flux equal to 12.4 kg/s m2. The distributor plate below the bundle enhanced the heat transfer, especially at lower vapor mass fluxes, by providing a level of liquid hold-up just below the bottom tube row. 相似文献
The aim of this study is to investigate the required refrigerant speed, hence minimum refrigeration load, for carrying the lubricating oil up in vertical sections of refrigerant lines. It is assumed that the downward flow of the thin oil layer over the inner surface of the riser due to gravity is to be balanced with the upward flow of the oil film due to the shear force created by the upward flow of the refrigerant vapor. Velocities are converted to refrigeration capacities by considering a saturated cycle between specified condenser and evaporator pressures. General relationships thus developed are enumerated for R134a by preparing minimum capacity tables for copper suction and discharge risers. 相似文献
Thermal acoustic oscillations are often observed in tubes which penetrate a cryogenic system and are closed at the warm end and open at the cold end. Such tubes are genrally used for filling or vetning the tank, providing relief pressure or inserting instruments taps. Large amounts of heat (of the order of ten to a thousand times more than by normal heat conduction) can be transferred into a cryogenic system when such thermaloscillations occur. A number of studies examining thermal acoustic oscillations in liquid helium systems have been performed by Rott et al. However, only minimal consideration has been given to such oscillationsin liquid and sluch hydrogen systems. This study extends Rott's theory to the stability aspects of thermal acoustic oscillations for a straight tube closed at the warm end and inserted into a Dewar flask filled with triple point liquid hydrogen when the cold open end is located above the liquid surface. These results can also be applied to a slush hydrogen when the pressure in the Dewar flask is reduced to the triple point pressure of hydrogen. Numerical results have been obtained in this study for developing stability curves, establishing oscillation frequency characteristics and identifying critical configurations for initiating such oscillation. The mechanisms associated with the two branches of the stability curves for thermal acoustic oscillations have also been investigated. 相似文献