Wind farms are considered to be negative loads from the point of view of a utility manager. Modern variable-speed wind turbines offer the possibility for controlling active and reactive power separately. This paper presents a new integrated control system of a wind farm according to the utility manager's requirements. This control system is based on two control levels: a supervisory system controls active and reactive power of the whole wind farm by sending out set points to all wind turbines, and a machine control system ensures that set points at the wind turbine level are reached. The system has been validated by numerical simulation using data from a wind farm with 37 variable-speed wind turbine situated in the North of Spain. An automatic generation control of these characteristics promises improved performance of the system and a better grid integration of the wind energy without significant extra costs  相似文献   