Mixing characteristics in a ventilated room with non-isothermal ceiling air supply |
| |
Affiliation: | 1. Department of Mechanical and Production Engineering, National University of Singapore, 10 Kent Ridge Crescent, Singapore 119260;1. Key Laboratory of Traffic Safety on Track, Ministry of Education, School of Traffic & Transportation Engineering, Central South University, Changsha 410075, Hunan, China;2. Institute of Disaster Prevention Science and Safety Technology, School of Civil Engineering, Central South University, Changsha 410075, Hunan, China;1. Building Technology and Urban Systems Division, Lawrence Berkeley National Laboratory, Berkeley, CA 94720, USA;2. Civil Engineering Department, IIT Madras, Chennai, 600 036, India;3. Department of Building, National University of Singapore, 4 Architecture Drive, SDE2, #03-10, 117566 Singapore |
| |
Abstract: | A two-dimensional turbulence k–ε model is used to predict distribution of air velocity, temperature and turbulence kinetic energy in an air-conditioned room using ceiling air supply. Mixing characteristics of the airflow are analyzed under different air supply velocities and temperatures. A modified Archimedes number is correlated with the parameters characterizing heat transfer, ventilation system, and turbulence kinetic energy of room air flow. Significant correlations have been shown. It is found that the linear ceiling air supply air-conditioning system with a high level return air provides excellent air mixing across a wide range of Archimedes numbers. The results are useful for air-conditioning design and thermal comfort study. |
| |
Keywords: | |
本文献已被 ScienceDirect 等数据库收录! |
|