衡水发电厂#1锅炉灭火原因分析
引用本文:安国银,张永红.衡水发电厂#1锅炉灭火原因分析[J].河北电力技术,2000,19(2):31-32,36.
作者姓名:安国银  张永红
作者单位:[1]河北省电力试验研究所 [2]衡水发电厂
摘    要:根据事故发生后所获得的历史曲线,从几方面分析了事故发生的原因。分析认为,锅炉灭火保护动俐因为送风系统发生了喘振,引起喘振的原因是由于对制粉系统的运行调整不当,对此笔者提出了切实可行的防范措施。

关 键 词:锅炉  灭火  制粉系统  喘振  发电厂

Cause Analysis on Fire-off of Boiler No. 1 in Hengshui Power Plant
An Guoyin,Liu Yonggang,Bian Jiang,et al.Cause Analysis on Fire-off of Boiler No. 1 in Hengshui Power Plant[J].Hebei Electric Power,2000,19(2):31-32,36.
Authors:An Guoyin  Liu Yonggang  Bian Jiang  
Affiliation:An Guoyin,Liu Yonggang,Bian Jiang,et al 31
Abstract:Based on the historical curves obtained after the accident, the causes of the accident are analyzed from all side of the event. The results indicate that surging of forced draft system initiates the boiler fireoff protection, and improper operational control of coalpulverizing system induces surging. From this, effective prevention measures are proposed.
Keywords:boiler  fire-off  coal pulverizing system  surging