外加电源方式100%定子接地保护的拒动与误动问题
引用本文:贺儒飞. 外加电源方式100%定子接地保护的拒动与误动问题[J]. 四川电力技术, 2005, 28(1): 29-31
作者姓名:贺儒飞
作者单位:广州蓄能水电厂,广东广州,510950
摘    要:分析了100%定子接地保护外加电源的频率对保护灵敏度的影响及其导致100%定子接地保护拒动的原因。此外还分析了特殊工况下,定子电流频率与100%定子接地保护误动的关系。并针对这两种情况分别提出了解决方案。

关 键 词:发电机定子  接地保护  故障  措施
文章编号:1003-6954(2005)01-0029-03
修稿时间:2004-11-13

Miss Operation and Malfunction Problem of Protection against Stator Ground 100% with Applied Power Source
He Rufei. Miss Operation and Malfunction Problem of Protection against Stator Ground 100% with Applied Power Source[J]. Sichuan Electric Power Technology, 2005, 28(1): 29-31
Authors:He Rufei
Abstract:The effect of the frequency of applied power source for protection against stator ground 100% on protection sensitivity and the reason caused the miss operation of protection against stator ground 100% have been analyzed. Besides, the relationship of stator current frequency and miss operation of protection against stator ground 100% in exceptional condition has been analyzed as well, and solutions corresponding to these two conditions have been proposed respectively.
Keywords:generator stator  grounding protection  failure  measures  