首页 | 本学科首页   官方微博 | 高级检索  
     

断路器合闸线圈烧毁原因分析与改进
引用本文:胡 浩,刘玉海,李元安.断路器合闸线圈烧毁原因分析与改进[J].山东电力技术,2014(2):52-53,59.
作者姓名:胡 浩  刘玉海  李元安
作者单位:国网山东省电力公司检修公司,山东临沂276000
摘    要:断路器跳合闸线圈烧毁是变电站综合自动化系统在运行中经常出现的问题,结合一起220 kV断路器合闸线圈烧毁事故,对其可能存在的原因进行探讨并初步分析。发现断路器跳合闸线圈烧毁可能由于合闸滚子和合闸掣子长期的摩擦,导致合闸滚子和合闸掣子脱离时的摩擦力增大引起。根据这一原因提出延时跳开合闸回路改进措施,同时对跳闸回路提出改进意见。

关 键 词:断路器  合闸线圈  辅助接点

Circuit Breaker Closing Coil Burning Cause Analysis and Improvement Measures
Abstract:The circuit breaker tripping coil burning substation automation system is in operation recurrent problem, this paper combined with the 220 kV circuit breaker closing coil burning accident, its possible causes are discussed and preliminarily analysed. Found that the circuit breaker tripping coil burning may be due to the closing roller and closing latch-term friction, resulting in the closing roller and closing the latch is disengaged due to increased friction. Based on this reason,this paper put forward several improvements on delay dosing loop jump.
Keywords:breaker  closing coil  auxiliary contacts
本文献已被 CNKI 维普 等数据库收录!