Performance characteristics of a MPCM slurry cooled unit designed for telecommunication equipment |
| |
Authors: | Jongmin Choi Jongug Jeon Yongchan Kim |
| |
Affiliation: | (1) Department of Mechanical Engineering, Hanbat National University, Duckmyung-Dong, Yusung-Gu, Daejeon, 305-719, Korea;(2) Department of Mechanical Engineering, Korea University, Anam-Dong, Sungbuk-Gu, Seoul, 136-701, Korea |
| |
Abstract: | Optimum control of the PCB surface temperature is very important in achieving high performance and operational reliability
of telecommunication equipment with high power density and thermal density. In this study, the performance of a liquid cooling
unit with MPCM slurries (called as “MPCM cooled unit”) was tested and analyzed. In addition, its performance was compared
with that of an air cooled unit and a water cooled unit. The maximum surface temperature and the index of uniform temperature
distribution (IUTD) were introduced to analyze cooling performance. The surface temperature in the unit rack of telecommunication
equipment can be controlled properly by using an MPCM cooled unit instead of an air cooled unit. The maximum surface temperature
and IUTD of the MPCM cooled unit at the inlet temperature of 19°C were lower than those at inlet temperatures of 25°C and
27°C due to the increases of heat capacity and heat transfer rate. The heat capacity of the MPCM cooled unit increased significantly
with the increase of mass flow rate due to high specific heat of MPCM particles with latent heat transfer rate. The cooling
performance of the MPCM cooled unit was superior to that of the water cooled unit. |
| |
Keywords: | MPCM Liquid cooling Heat density Telecommunication equipment |
本文献已被 SpringerLink 等数据库收录! |
|