首页 | 本学科首页   官方微博 | 高级检索  
     


Application of a distance relaying scheme to compensate fault location errors due to fault resistance
Authors:N. El Halabi,M. Garcí  a-GraciaS. Martí  n Arroyo,A. Alonso
Affiliation:Centre of Research for Energy Resources and Consumption (CIRCE)/Mariano Esquillor, 15/50018 Zaragoza, Spain
Abstract:This paper proposes a distance relaying scheme based on the current phase jump behavior during fault conditions to improve the apparent impedance estimated by the distance relay. For a nonpilot protection scheme, the measured impedance is affected by error due to the combined effects of fault resistance and prefault load. An experimental relation between the current phase jump introduced with fault inception and the X/R ratio seen by the distance protection is deduced. The phase jump correction factor obtained is an exponential function of the X/R ratio of the line. This factor is applied to the apparent impedance measured by the relay and it allows mitigating the adverse effect of prefault power. The relaying scheme improves significantly the accuracy in estimation of the resistive fault location. The application of this scheme does not require communication links from the remote end of line and is applicable to all types of fault.
Keywords:Adaptive scheme   Distance protection   Impedance locus   Fault resistance   Prefault load   Current phase jump
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号