Power swing analysis in a future metropolitan electric power system on a contingent trip of cryogenic high-power cables
Authors:Naoki Hayakawa  Yukio Kito  Toshiro Matsumura
Abstract:A cryogenic power cable is expected to be capable of carrying bulk power as a main transmission line in a future metropolitan electric power system. It is important to establish a strategy of how to sustain power supply when such a highly densified power supply route trips from the network due to contingency. It is proposed here that the bulk power transmitted by the cryogenic cable could be distributed into the parallel conventional transmission lines by suitable circuit breaker operations in the system. In this process, power-flow routes are forced to be changed with a remarkable modification in the system configuration. In this paper, the power swings associated with the large power-flow change following contingent faults are analyzed by means of a transient network analyzer. It is found that the proposed system modification could be realized without any harmful power swing if the parameters in generators as well as in control devices have conventional magnitudes. It is shown also by simulations that the margin to occurrence in an unstable power swing is left sufficient even if the parameters deviate somewhat from the present magnitudes.