首页 | 本学科首页   官方微博 | 高级检索  
     


Removal of Contaminants from Underground Spaces by Induced Ventilation
Authors:G. Ziskind  V. Dubovsky  R. Letan
Affiliation:1Lecturer, Heat Transfer Laboratory, Dept. of Mechanical Engineering, Ben-Gurion Univ. of the Negev, Post Office Box 653, Beer-Sheva?84105, Israel.
2Research Engineer, Heat Transfer Laboratory, Dept. of Mechanical Engineering, Ben-Gurion Univ. of the Negev, Post Office Box 653, Beer-Sheva?84105, Israel.
3Professor and Head, Heat Transfer Laboratory, Dept. of Mechanical Engineering, Ben-Gurion Univ. of the Negev, Post Office Box 653, Beer-Sheva?84105, Israel.
Abstract:The present paper introduces induced airflow as an effective means for removal of contaminants from underground enclosed spaces. The airflow is caused by natural convection in a vertical duct which absorbs solar irradiation outside the building. Experimental studies and three-dimensional numerical simulations have been performed in a scaled-down laboratory model. The experiments included temperature and velocity measurements and flow visualization. The results obtained from the simulations are fully supported by the experimental results, indicating that effective ventilation by the proposed method is achievable. For real-size structures, three-dimensional computer simulations have been performed using a standard k-ε turbulence model. The results yield a detailed flow field inside the enclosure for various configurations of the ducts and partitions. Rate of air change is calculated both for the whole enclosure, and for the regions above the floor where contaminants like radon tend to accumulate. By adjustment of openings in the basement, the ceiling may be cleared of contaminants as well. It is shown that a properly designed structure, even at low solar fluxes, can provide adequate ventilation of a real-size underground enclosure.
Keywords:Abatement and removal  Contaminants  Ventilation  Underground structures  Air flow  
设为首页 | 免责声明 | 关于勤云 | 加入收藏