An improved control algorithm of shunt active filter for voltageregulation, harmonic elimination, power-factor correction, and balancingof nonlinear loads
Authors:Chandra  A Singh  B Singh  BN Al-Haddad  K
Affiliation:Dept. of Electr. Eng., Ecole de Technol. Superieure, Montreal, Que.;
Abstract:This paper deals with an implementation of a new control algorithm for a three-phase shunt active filter to regulate load terminal voltage, eliminate harmonics, correct supply power-factor, and balance the nonlinear unbalanced loads. A three-phase insulated gate bipolar transistor (IGBT) based current controlled voltage source inverter (CC-VSI) with a DC bus capacitor is used as an active filter (AF). The control algorithm of the AF uses two closed loop PI controllers. The DC bus voltage of the AF and three-phase supply voltages are used as feedback signals in the PI controllers. The control algorithm of the AF provides three-phase reference supply currents. A carrier wave pulse width modulation (PWM) current controller is employed over the reference and sensed supply currents to generate gating pulses of IGBTs of the AF. Test results are presented and discussed to demonstrate the voltage regulation, harmonic elimination, power-factor correction and load balancing capabilities of the AF system
Keywords: