一次发电机失磁引起的系统保护失误
引用本文:刘敏,苏忠阳. 一次发电机失磁引起的系统保护失误[J]. 广东输电与变电技术, 2008, 0(3): 35-36
作者姓名:刘敏  苏忠阳
作者单位:广东电网公司广州供电局
摘    要:同步发电机在失磁状况下会发生一系列的电气变化.结合华侨糖厂发电机在失磁时导致上一级馈线系统侧跳闸的事故,对发电机失磁时的电气量变化进行了定量计算,进而得出发电机失磁故障可能造成系统侧相关电流保护动作的结论.

关 键 词:发电机失磁  励磁  电网失步

A Lapsus of System Protection arose by Generator's Excitation Loss
Liu Min,Su Zhongyang. A Lapsus of System Protection arose by Generator's Excitation Loss[J]. Guangdong Power Transmission Technology, 2008, 0(3): 35-36
Authors:Liu Min  Su Zhongyang
Affiliation:Liu Min Su Zhongyang Guangdong Power Grid Corporation Guangzhou Power Supply Bureau
Abstract:Under excitation loss condition,synchronous generator will take a series of electric change.Combining with leading to tripping event of the last level feeder system during excitation loss of generator in Huatang Power Plant,calculated out electrical change,and got conclusion:when the generator is loss of excitation,related current relay will trip in system side.
Keywords:Generator's excitation loss  Excitation  Out of step