首页 | 本学科首页   官方微博 | 高级检索  
     


A comprehensive design and performance evaluation study of counter flow wet cooling towers
Authors:Jameel-Ur-Rehman Khan   Bilal Ahmed Qureshi  Syed M. Zubair  
Affiliation:

Department of Mechanical Engineering, King Fahd University of Petroleum and Minerals, P.O. Box #1474, Dhahran 31261, Saudi Arabia

Abstract:Fouling of cooling tower fills is one of the most important factors affecting its thermal performance, which reduces cooling tower effectiveness and capability with time. In this paper, the fouling model presented in an earlier paper using the experimental data on fill fouling, is used to investigate the risk based thermal performance of the cooling tower. It is demonstrated that effectiveness of the cooling tower degrades significantly with time indicating that for a low risk level (p=0.01), there is about 6.0% decrease in effectiveness for the given fouling model. The sensitivity analysis of the cooling tower is investigated for both rating and design calculation for different values of mass flow rate ratios. The effect of atmospheric pressure on the thermal performance of the cooling tower is also demonstrated.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏