摘    要:小电流接地系统的安全运行对配电网来说是很重要的,它的故障选线问题是关键.在配电网不同的运行方式下,分析了小电流接地系统的稳态故障特征,并对零序电流比幅比相法和五次谐波选线法,进行了仿真.仿真结果表明,在不同运行方式下2种方法可进行互补,可准确、快速地选线,但受到接地电阻和线路长短的影响,且零序电流也受到消弧线圈补偿作用的影响.

关 键 词:小电流接地系统  故障选线  零序电流  五次谐波

Analysis of Fault Line Selection in Small Current Grounding Power System
ZHANG Xiao-tao,QIAO Xiao-mei,WANG Ai-jun.Analysis of Fault Line Selection in Small Current Grounding Power System[J].Journal of North China Institute of Water Conservancy and Hydroelectric Power,2010,31(6):89-93.
Authors:ZHANG Xiao-tao  QIAO Xiao-mei  WANG Ai-jun
Affiliation:(North China Institute of Water Conservancy and Hydroelectric Power,Zhengzhou 450011,China)
Abstract:The safe operation of the small current grounding system is important for distribution networks and the fault line selection is key.Based on different operational modes of the distribution,the characteristics of steady-state fault of the small current grounding power system were analyzed and simulation was done on the line selection methods of the zero sequence current comparing phase and amplitude and the fifth harmonic.Simulation results showed that the two kinds of methods in different operational modes could be complementary,select fault line exactly and rapidly.But they were influenced by grounding resistance and line length,and zero sequence current was also affected by coil compensation.
Keywords:small current grounding power system  fault line selection  zero sequence current  fifth harmonic