首页 | 本学科首页   官方微博 | 高级检索  
     

某银行计算机中心电气故障解决案例
引用本文:程绍颐,冯志文. 某银行计算机中心电气故障解决案例[J]. 建筑电气, 2009, 28(6): 19-20
作者姓名:程绍颐  冯志文
作者单位:甘肃省建筑设计研究院,兰州市,730030;陕西省建筑设计研究院有限责任公司,西安市,710003
摘    要:介绍了某银行计算机中心电气故障的分析过程和解决措施。UPS保护开关连同外部保护开关多次发生故障跳闸,分析其原因为:①TN—C—S系统中N线与PE线分开后又合并;②三相负荷不平衡;③谐波影响。

关 键 词:电气故障  接地  三相负荷不平衡  N线对地电压  中性点偏移  谐波

Solution Case for the Electrical Fault in a Bank Computer Center
Cheng Shaoyi,Feng Zhiwen. Solution Case for the Electrical Fault in a Bank Computer Center[J]. Building Electricity, 2009, 28(6): 19-20
Authors:Cheng Shaoyi  Feng Zhiwen
Affiliation:Gansu Institute of Architectural Design & Research;Lanzhou 730030;China;Shanxi Architectural Design & Research Institute Co.;Ltd.;Xi'an 710003;China
Abstract:The analysis process and solutions for the electrical fault in a bank computer center are introduced. UPS switch along with the external protection switch tripped many times because of fault, the causes of which are that: (1) the N conductor and the PE conductor in the TN-C-S system are first separated and then combined; (2)three-phase load is unbalanced; (3) harmonic impact.
Keywords:Electrical fault Grounding Three-phase load unbalance Voltage between N conductor and ground Neutral point offset Harmonics  