首页 | 本学科首页   官方微博 | 高级检索  
     


The field test of a cable internally cooled with fire resistant oil
Authors:Ogawa  K Kurata  M Suzuki  H Ichiyanagi  N Nakayama  K Inoue  T Kasuya  M Iwata  Z
Affiliation:Tokyo Electr. Power Co. Inc.;
Abstract:Tricresyl phosphate (TCP), a phosphate ester with fire-resistant and insulating properties, is proposed as a cable cooling medium. A field test was performed with a 275 kV internally-oil-cooled, oil-filled (OF) power cable system using TCP, and it was ascertained that the cable system meets requirements for ease of installation, cooling characteristics, and long-term stability of the cable and the long-term stability of the cable and the TCP. The series of tests has demonstrated the practicality of the cable system