电流互感器5%误差曲线测试数据的矫正 |
| |
引用本文: | 赵晓明,余志慧.电流互感器5%误差曲线测试数据的矫正[J].浙江电力,2014(5):45-47. |
| |
作者姓名: | 赵晓明 余志慧 |
| |
作者单位: | [1]华北电力大学,北京102206; [2]国网浙江省电力公司电力科学研究院,杭州310014; [3]国网浙江省电力公司杭州供电公司,杭州310016 |
| |
摘 要: | 在进行TA(电流互感器)5%误差曲线测试时,发现用OMICRON TA测试仪得出的数据失真。利用TA励磁曲线数据,重新对5%误差曲线进行了手工计算,得出了矫正后的数据曲线。通过对不同TA测试数据的分析和对比,指出此测试仪在5%误差曲线绘制时可能存在拟合错误。
|
关 键 词: | 电流互感器 5%误差曲线 励磁曲线 |
Measurement Data Correction of 5%Error Curve of Current Transformer |
| |
Affiliation: | ZHAO Xiaoming, YU Zhihui (1. North China Electric Power University, Beijing 102206, China; 2. State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China; 3. State Grid Hangzhou Power Supply Company, Hangzhou 310016, China) |
| |
Abstract: | This paper introduces a 5%error curve test case of TA (current transformer) in a power plant and finds that there is data distortion obtained by OMICRON TA tester. By using excitation curve data of TA , 5%error curve is manually recalculated and data curve after correction is then obtained. By analyzing and com-paring different TA test data, the paper points out probable matching error while the tester draws 5% error curve. |
| |
Keywords: | current transformer 5%error curve excitation curve |
本文献已被 CNKI 维普 等数据库收录! |
|