首页 | 本学科首页   官方微博 | 高级检索  
     


Dielectric characteristics of turn-to-turn insulation models of gas-insulated transformer under very fast transient voltages
Authors:Tamotsu Inoue  Tsuneharu Teranishi  Yasuhiko Taniguchi  Katsutoshi Toda  Toshiyuki Yanari
Abstract:This paper deals with the partial discharge inception voltage (PDIV) and breakdown voltage (BDV) characteristics of turn-to-turn insulation models for SF6 gas-insulated transformers in the presence of steep-front short-pulse voltages, whose waveforms are 35/65 ns and 50/370 ns. It was determined that PDIV at nanosecond pulses were 1.05 to 1.15 times higher than those at standard impulse voltages and that the BDV at nanosecond pulses were about 1.4 times higher than those at standard impulse voltages. The ratio of impulse PDIV to ac PDIV is 1.40 to 1.48 for standard impulse voltages and 1.32 to 1.37 for switching impulses. © 1998 Scripta Technica, Inc. Electr Eng Jpn, 121(3): 36–43, 1997
Keywords:SF6 gas  turn-to-turn model  gas-insulated transformer  steep-front short-duration pulse voltage  partial discharge  breakdown
设为首页 | 免责声明 | 关于勤云 | 加入收藏