首页 | 本学科首页   官方微博 | 高级检索  
     

基于PSO-ELM的变压器油纸绝缘状态无损评估方法研究
引用本文:张德文,张健,曲利民,吴迪星,刘贺千,张明泽. 基于PSO-ELM的变压器油纸绝缘状态无损评估方法研究[J]. 电力工程技术, 2024, 43(3): 201-208
作者姓名:张德文  张健  曲利民  吴迪星  刘贺千  张明泽
作者单位:国网黑龙江省电力有限公司电力科学研究院,国网黑龙江省电力有限公司电力科学研究院,国网黑龙江省电力有限公司电力科学研究院,哈尔滨理工大学,国网黑龙江省电力有限公司电力科学研究院,哈尔滨理工大学,
基金项目:国家电网有限公司总部科技项目(5500-202330167A-1-1-ZN)
摘    要:油浸式电力变压器作为电网中的重要组成部分,其可靠运行至关重要。针对变压器长期运行后无法定量评估其绝缘状态的问题,本文开展了油纸绝缘模型的加速老化及受潮试验,探明了油纸绝缘老化及受潮程度对其回复电压曲线的影响规律,并提出采用粒子群优化(PSO)改进极限学习机(ELM)的参数预测方法,实现了基于回复电压曲线特征参量的油纸绝缘老化与受潮状态量化评估。通过对油纸绝缘模型理化性能分析的对比结果可知,基于PSO-ELM方法的预测值精度远高于传统ELM方法,油纸绝缘内含水率及纸板聚合度预测的绝对误差范围分别小于±0.4%、±30。

关 键 词:油浸式变压器;油纸绝缘;回复电压;PSO-ELM算法;状态评估;无损检测
收稿时间:2023-04-28
修稿时间:2023-08-08

Study on the assessment method of transformer oil-paper insulation state based on PSO-ELM
Zhang Dewen,Zhang Jian,Qu Limin,Wu Dixing,Liu Heqian,Zhang Mingze and. Study on the assessment method of transformer oil-paper insulation state based on PSO-ELM[J]. Electric Power Engineering Technology, 2024, 43(3): 201-208
Authors:Zhang Dewen  Zhang Jian  Qu Limin  Wu Dixing  Liu Heqian  Zhang Mingze and
Affiliation:Electric Power Research Institute,State Grid Heilongjiang Electric Power Company Limited,Electric Power Research Institute,State Grid Heilongjiang Electric Power Company Limited,Electric Power Research Institute,State Grid Heilongjiang Electric Power Company Limited,Key Laboratory of Engineering Dielectrics and Its Application Ministry of Education,Harbin University of Science and Technology,Electric Power Research Institute,State Grid Heilongjiang Electric Power Company Limited,Key Laboratory of Engineering Dielectrics and Its Application Ministry of Education,Harbin University of Science and Technology,
Abstract:Oil-immersed power transformer is an important part of power grid, that reliable operation is very important. Aiming at the problem that the insulation state of transformer cannot be assessed quantitatively after long-term operation, the accelerated aging and damp tests of oil-paper insulation model were carried out in this paper. The influence of aging and damp of oil-paper insulation on its recovery voltage curves were explored. The particle swarm optimization (PSO) was used to improve the parameter prediction method of Extreme Learning Machine (ELM), which realized the quantitative assessment of aging and moisture of oil-paper insulation based on the characteristic parameters of the recovery voltage curve. By comparing the physical and chemical performance analysis of oil-paper insulation models, it can be seen that the prediction accuracy based on PSO-ELM method is much higher than that of traditional ELM method. The absolute error range for predicting the moisture content of oil-paper insulation and the DP of pressboard is less than ± 0.4% and ± 30 respectively.
Keywords:Oil-immersed transformer   Oil-paper insulation   Return voltage   PSO-ELM algorithm   State assessment   Non-Destructive Testing
点击此处可从《电力工程技术》浏览原始摘要信息
点击此处可从《电力工程技术》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号