Abstract: | A new fault location system using optical current transducers (CTs) to detect faulted sections in the bus bars of directly grounded 275-kV substations has been developed. This system detects fault current by combining optical CTs with wound-type CTs. The new type of optical CT applies a bulk-type Faraday sensor to the combination of windings around a magnetic iron core and a solenoid coil. The optical CT was capable of current measuring over 50 kA. A current differential discriminator combining an optical CT and a wound-type CT verified the operational performance with 40-kA currents. The intended level of fault detection performance was obtained. Based on these results, a system is being made for actual application in 275-kV substations. © 1997 Scripta Technica, Inc. Electr Eng Jpn 119(2): 10–17, 1997 |