Local optimal load-shedding with allowance for voltage deviation
Authors:Goro Fujita  Goro Shirai
Abstract:This paper describes an optimal load-shedding method which can be applied to local buses in order to suppress voltage deviations, based on local information obtained at each bus. When a generation outage occurs, adequate amounts of loads must be shed within a few seconds in order to maintain the balance between supply and demand. This method is able to decide quickly the optimal amounts of loads to be shed after the fault. The proposed method is based on the fact that the location of the fault can be estimated exclusively from power flow deviations at local buses, measured after the outage. Because the amounts of load to be shed have constraints, it is necessary to find the optimal factors which decide the amounts of load-shedding at each bus by quadratic programming. To solve this problem we first linearize the study system. Next, in order to relate power flows to voltage deviations at each bus, the voltage sensitivity factors obtained by ac power flow calculation are evaluated. Numerical simulations with 4-machine and 9-machine power system models show the effectiveness of the proposed method. It distributes adequate loads which are almost identical to the completely optimized loads, and it produces smaller voltage deviations than the conventional method. Improved transient characteristics of voltage deviations are also demonstrated. © 1997 Scripta Technica, Inc. Electr Eng Jpn 119(1): 35–44, 1997
Keywords:power generation outage  load-shedding  optimization  quadratic programming  power flow calculation  voltage sensitivity coefficient