Experimental study of water mist fire suppression in tunnels under longitudinal ventilation
Authors:Lvyi Chen  Wei Zhu  Xin Cai  Liwei Pan  Guangxuan Liao
Affiliation:1. State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei, Anhui, China;2. Beijing Research Center of Urban System Engineering, Beijing, China;3. Department of Building and Construction, City University of Hong Kong, Hong Kong, China
Abstract:This paper studies water mist fire suppression under different longitudinal ventilation velocities in tunnels by small-scale experiments. After a scaling study, two mist nozzles are used for suppressing crib fires under 5 ventilation speeds. The result comes out that fire suppression process can be divided into three stages including flame unitary restraining stage, surface flame extinguishing stage and inside flame suppression stage. Several factors influencing efficiency are investigated. When the interval between mist nozzle and fire source enlarges, the relationship curve between fire suppression time and ventilation velocity shows a ‘V’ figure. The best ventilation speed exists. Following the rules summarized, a coupling system of water mist and ventilation may increase fire suppression efficiency remarkably.
Keywords:Water mist   Fire suppression   Longitudinal ventilation   Scaling study   Tunnels