Effect of ambient conditions on the first and second law performance of an open desiccant cooling process
Authors:Mehmet Kano  lu, Ali Bolattü  rk,Necdet Altuntop
Affiliation:aDepartment of Mechanical Engineering, University of Gaziantep, 27310 Gaziantep, Turkey;bDepartment of Mechanical Engineering, Süleyman Demirel University, 32260 Isparta, Turkey;cDepartment of Mechanical Engineering, Erciyes University, 38039 Kayseri, Turkey
Abstract:An open desiccant cooling process is presented and applied to ventilation and recirculation modes of the system operation. The cooling system consists of a desiccant wheel, a rotary regenerator, two evaporative coolers, and a heating unit. Certain ideal operating characteristics based primarily on the first law of thermodynamics are assumed for each component. The system with indoor and outdoor ARI conditions has a thermal coefficient of performance (COP) of 1.17 in ventilation mode and 1.28 in recirculation mode. A second law analysis is also performed and at ARI conditions, the reversible COP of the system is determined to be 2.63 in ventilation mode and 3.04 in recirculation mode. Variation of the first and second law based COP terms and cooling load with respect to ambient temperature and relative humidity are investigated in both modes of the system operation. The results of the analysis provide an upper limit for the system performance at various ambient conditions and may serve as a model to which actual desiccant cooling systems may be compared. As an additional study, a non-ideal system operation is considered and it is determined that both the COP and cooling load decrease with increasing ambient temperature and relative humidity, and they approach zero at high values of ambient temperature and humidity.
Keywords:Desiccant   Cooling   Refrigeration   Air-conditioning   Second-law analysis
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号