高轴压比、低剪跨比双钢板-混凝土组合剪力墙拟静力试验研究
引用本文:聂建国, 卜凡民, 樊健生. 高轴压比、低剪跨比双钢板-混凝土组合剪力墙拟静力试验研究[J]. 工程力学, 2013, 30(6): 60-66. DOI: 10.6052/j.issn.1000-4750.2011.09.0587
作者姓名:聂建国  卜凡民  樊健生
作者单位:1.清华大学土木工程安全与耐久教育部重点实验室,北京100084;;2.中国建筑科学研究院,北京100013
基金项目:国家自然科学基金项目(51178246);清华大学自主科研计划项目(20101081766)
摘    要:双钢板-混凝土组合剪力墙可减小墙体厚度、提高承载力和延性,为研究双钢板-混凝土组合剪力墙高轴压比下的抗震性能,完成了5个剪跨比为1.0的双钢板-混凝土组合剪力墙试件的拟静力试验,研究了剪力墙在低周往复荷载作用下的受力性能和破坏模式等,分析了轴压比、距厚比等因素对抗震性能的影响。试验结果表明:低剪跨比试件发生弯剪破坏;墙体钢板在平均位移角1/83时发生局部屈曲,初始屈曲形态受距厚比影响显著;试件峰值荷载、位移延性系数、刚度等受轴压比、距厚比的影响较小;试件平均极限位移角达1/72、平均有效破坏位移角达1/52,具有良好的变形能力;距厚比增大,试件滞回性能稳定性降低;试件耗能随变形增大而迅速增长,抗震性能良好。建议低剪跨比双钢板-混凝土组合剪力墙轴压比限值取0.7。

关 键 词:双钢板-混凝土组合剪力墙  高轴压比  低剪跨比  拟静力试验  抗震性能
收稿时间:2013-06-27
修稿时间:2013-06-27

Quasi-static test on low shear-span ratio composite shear wall with double steel plates and infill concrete under high axial compression ratio
NIE Jian-guo, BU Fan-min, FAN Jian-sheng. Quasi-static test on low shear-span ratio composite shear wall with double steel plates and infill concrete under high axial compression ratio[J]. Engineering Mechanics, 2013, 30(6): 60-66. DOI: 10.6052/j.issn.1000-4750.2011.09.0587
Authors:NIE Jian-guo  BU Fan-min  FAN Jian-sheng
Affiliation:1.Key Laboratory of Civil Engineering Safety and Durability of China Education Ministry,Tsinghua University,Beijing 100084,China;;2.China Academy of Building Research,Beijing 100013,China
Abstract:The composite shear wall with double steel plates and infill concrete has advantages of reducing wall thickness and increasing capacity and ductility.In order to study the seismic performance of a composite shear wall with double steel plates and infill concrete under a high axial compression ratio,quasi-static tests on five composite shear walls with double steel plates and infill concrete of the shear span ratio of 1 were conducted.The seismic performance and failure modes were observed under low cyclic lateral loads,and the axial compression ratio and distance to thickness ratio on the seismic performance were analyzed.The results indicate that the failure mode of specimens is the flexural-shear failure.Local buckling occurs when the average displacement angle reaches 1/83,and the form of initial buckling is significantly affected by the distance to thickness ratio of steel plate.The specimen peak load,displacement ductility factor and stiffness are less influenced by axial compression ratio and distance to thickness ratio.The average ultimate displacement angle of the specimens reaches 1/72,and the average effective failure displacement angle is up to 1/52,showing good deformability.The stability of hysteretic behavior of the specimens reduces with the distance to thickness ratio increased.Energy dissipation capacity increases rapidly with the increase of deformation,showing a good seismic performance.The axial compression ratio of a low shear-span ratio composite shear wall with double steel plates and infill concrete is recommended to take 0.7.
Keywords:composite shear wall with double steel plates and infill concrete  high axial compression ratio  low shear-span ratio  quasi-static test  seismic performance