首页 | 本学科首页   官方微博 | 高级检索  
     


Critical Length Criterion and the Arc Chain Model for Calculating the Arcing Time of the Secondary Arc Related to AC Transmission Lines
Abstract:The prompt extinction of the secondary arc is critical to the single-phase reclosing of AC transmission lines,including half-wavelength power transmission lines.In this paper,a lowvoltage physical experimental platform was established and the motion process of the secondary arc was recorded by a high-speed camera.It was found that the arcing time of the secondary arc rendered a close relationship with its arc length.Through the input and output power energy analysis of the secondary arc,a new critical length criterion for the arcing time was proposed.The arc chain model was then adopted to calculate the arcing time with both the traditional and the proposed critical length criteria,and the simulation results were compared with the experimental data.The study showed that the arcing time calculated from the new critical length criterion gave more accurate results,which can provide a reliable criterion in term of arcing time for modeling and simulation of the secondary arc related with power transmission lines.
Keywords:AC transmission lines  secondary arc  arcing time  dynamic modeling  critical length criterion  
本文献已被 CNKI 等数据库收录!
点击此处可从《等离子体科学和技术》浏览原始摘要信息