Zero-sequence representation of overhead lines
Authors:Dipl Ing Dr Techn J M Nahman
Affiliation:(1) Faculty of Electrical Engineering, University of Belgrade, Bul. Revolucije 73, PO Box 816, 11001 Belgrade, Yugoslavia
Abstract:Contents The zero sequence components of electrical quantities of overhead lines appearing at unsymmetrical ground faults are analysed, taking into account the mutual coupling among line phase circuits and earth wires as well as the conducting effects of line towers. The line model, developed using the Z-Transform, enables an accurate analysis of ground fault current distribution and magnitudes. As an illustration, the line model is applied for evaluation of various earthing system parameters of an EHV line connecting two substations. Analytical expressions for some of these parameters are also given.
Nullsystem-Darstellung von Freileitungen
Übersicht Die Nullkomponente der elektrischen Größen, die etwa bei unsymmetrischen Erdkurzschlüssen auf Freileitungen vorkommen, werden unter Berücksichtigung der elektromagnetischen Kopplungen zwischen den Hauptleitern und den Erdseilen sowie der Mastströme analyisert. Das unter Verwendung der Z-Transformation entwickelte Leitungsmodell ermöglicht eine genaue Bestimmung der Verteilung und der Größe der Erdkurzschlußströme. Als Beispiel wird es zur Berechnung verschiedener Erdungsparameter einer Höchstspannungsfreileitung angewandt, die zwei Umspannwerke verbindet. Analytische Formeln für einige dieser Parameter werden angegeben.

List of Principal Symbols i vector of triple zero-sequence currents of line circuits - i ek total earth wire current at spank - i ek vector of earth wire currents at spank - u k vector of zero-sequence potentials of line circuits at towerk - u ek potential of towerk - u p voltage of the faulted phase, prior to fault occurence - zp matrix of self- and mutual-impedances of line circuits, per line span - z m matrix of mutual impedances among line circuits and earth wires, per line span - z matrix of self- and mutual-impedances of earth wires, per line span - Z +,Z ,Z 0 positive-, negative- and zero-sequence impedances - Z A (Z B ) resistance to ground of substationA(B) carthing grid - Z l carth wire ground resistance - R tower resistance to ground - mgr earth wire coupling factor - r earth wire total screening factor - M(N) number of line circuits (earth wires) - M(N) M(N)-dimensional vector of units
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号