涌流工况下换流变压器零序差动保护误动对策
引用本文:翁汉琍,郭祎达,李昊威,万毅,李振兴,黄景光. 涌流工况下换流变压器零序差动保护误动对策[J]. 电力系统自动化, 2020, 44(23): 143-149
作者姓名:翁汉琍  郭祎达  李昊威  万毅  李振兴  黄景光
作者单位:1.梯级水电站运行与控制湖北省重点实验室(三峡大学),湖北省宜昌市 443002;2.国网甘肃省电力公司检修公司,甘肃省兰州市 730000;3.中国长江电力股份有限公司,湖北省宜昌市 443002
基金项目:国家自然科学基金资助项目(51607106);国家留学基金资助项目(201908420183)。
摘    要:针对高压直流输电工程中换流变压器零序差动保护误动的案例,采用基于工程实际参数的高压直流输电仿真模型,对换流变压器外部故障切除恢复性涌流及空载合闸励磁涌流导致中性线零序电流幅值较大且衰减缓慢的现象进行了仿真分析。通过识别中性线零序电流与自产零序电流波形呈现出的相似度特征在涌流工况和区内故障时的差异,提出了基于零序电流动态时间弯曲距离的换流变压器零序差动保护新判据。经仿真算例和录波案例验证,该判据在各类区内故障时具有与传统零序差动保护相同的保护范围及抗过渡电阻能力,可以正确辨识涌流工况下电流互感器传变异常引起的虚假差动电流,进而降低零序差动保护误动风险。

关 键 词:换流变压器  励磁涌流  恢复性涌流  零序差动保护  动态时间弯曲距离
收稿时间:2019-12-16
修稿时间:2020-07-15

Countermeasures for Mal-operation of Zero-sequence Differential Protection of Converter Transformer Under Inrush Current Condition
WENG Hanli,GUO Yid,LI Haowei,WAN Yi,LI Zhenxing,HUANG Jingguang. Countermeasures for Mal-operation of Zero-sequence Differential Protection of Converter Transformer Under Inrush Current Condition[J]. Automation of Electric Power Systems, 2020, 44(23): 143-149
Authors:WENG Hanli  GUO Yid  LI Haowei  WAN Yi  LI Zhenxing  HUANG Jingguang
Affiliation:1.Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station (China Three Gorges University), Yichang 443002, China;2.State Grid Gansu Maintenance Company, Lanzhou 730000, China;3.China Yangtze Power Co., Ltd., Yichang 443002, China
Abstract:Aiming at the case of mal-operation of zero-sequence differential protection for the converter transformer in the high voltage direct current (HVDC) transmission project, this paper analyzes the phenomenon that the neutral-line zero-sequence current has a large amplitude and decays slowly under the recovery inrush current condition caused by removal of external faults and the inrush current condition caused by the energization of unloaded converter transformers, based on the HVDC simulation model using actual engineering parameters. By identifying differences in similarity characteristics between the waveforms of neutral-line zero-sequence current and the self-produced zero-sequence current under inrush current and internal fault conditions, this paper proposes a new criterion of the zero-sequence differential protection for converter transformers, based on the dynamic time warping (DTW) distance of zero-sequence current. The simulation and recorded cases show that the criterion has the same operation performance as the conventional zero-sequence differential protection in aspects of protecting range and transition resistance endurance ability during various internal faults. The false differential current caused by abnormal transmission of current transformers under the inrush current condition can be correctly identified, and the risk of mal-operation of zero-sequence differential protection can be reduced.
Keywords:converter transformer  magnetizing inrush current  recovery inrush current  zero-sequence differential protection  dynamic time warping (DTW) distance