10 kV级晶闸管控制电容无功补偿装置的研制和试验
引用本文:王民慧,李民族,王武,王世蓉,尉学军,杨艳,汤加仕. 10 kV级晶闸管控制电容无功补偿装置的研制和试验[J]. 中国电力, 2016, 49(4): 67-72. DOI: 10.11930/j.issn.1004-9649.2016.04.067.06
作者姓名:王民慧  李民族  王武  王世蓉  尉学军  杨艳  汤加仕
作者单位:1. 贵州大学 电气工程学院,贵州 贵阳 550025; 2. 贵州理工学院 电气工程学院,贵州 贵阳 550003; 3. 贵州中泉电气集团有限公司,贵州 贵阳 550014
基金项目:贵州省科技计划项目(黔科合GY字(2005)3019);贵阳市科技计划项目([2006]筑科工合同字第16-5号)~~
摘    要:为使晶闸管控制电容(TCC)无功补偿装置进入实用,研制了一台10 kV 级TCC装置,并投入试运行。设计制作了一次接线装置和控制保护装置; 进行了有关电压、电流的稳态特性和暂态特性的测试; 进行了自动调节母线电压、进线cos φ和进线无功试验; 测试了系统响应时间。测试、试验和试运行结果表明,该装置无功电压调节满足设计要求,对电网不产生高次谐波,投切和换级时冲击电流小,换级过程时间小于10 ms,系统响应时间为30~40 ms,能快速频繁调节电压、功率因数和进线无功。经优化设计,装置单位容量造价可接近于机械式投切电容器(MSC)。

关 键 词:无功补偿  快速调节  晶闸管  控制电容器  TCC  
收稿时间:2015-05-08

Development of 10 kV Thyristor Controlled Capacitor (TCC) Dynamic Var Compensator
WANG Minhui;LI Minzu;WANG Wu;WANG Shirong;WEI Xuejun;YANG Yan;TANG Jiashi. Development of 10 kV Thyristor Controlled Capacitor (TCC) Dynamic Var Compensator[J]. Electric Power, 2016, 49(4): 67-72. DOI: 10.11930/j.issn.1004-9649.2016.04.067.06
Authors:WANG Minhui  LI Minzu  WANG Wu  WANG Shirong  WEI Xuejun  YANG Yan  TANG Jiashi
Affiliation:1. College of Electrical Engineering, Guizhou University, Guiyang 550025, China; 2. Electrical Engineering College, Guizhou Institute of Technology, Guiyang 550003, China; 3. Zhongquan Electric Group, Guiyang 550014, China
Abstract:A Thyristor Controlled Capacitor (TCC) Dynamic Var Compensator is developed and put into trial operation. The primary electric wiring device is designed, and related control and protection device is also developed. The steady state characteristics and transient behaviors of corresponding voltage and current of device are tested. Automatic voltage regulation, automatic power factor change and reactive power regulation experiments are completed under 10 kV voltage. The device response time is also tested. Test results show that reactive power regulation of device meets design requirements. There are small impact current(rush current, surge current) and no high order harmonic waves at device switching. The changing stage time is less than 10 ms. The system response time of this device is 30~40 ms. It can realize voltage regulation, power factor and reactive power regulation quickly and frequently. It can be put into practical application. Further optimization can reduce device cost per MV·A close to MSC level.
Keywords:var compensation   quick regulation   thyristor   controlled capacitor   TCC  