Effects of DC testing on AC breakdown strength of XLPE insulatedcables subjected to laboratory accelerated aging |
| |
Authors: | Srinivas NN Bernstein BS Decker RA |
| |
Affiliation: | Detroit Edison Co., MI; |
| |
Abstract: | The results of a study performed on crosslinked polyethylene (XLPE) insulated cables tested in the laboratory under accelerated conditions are described. URD-type cables rated at 15 kV were aged at 60 Hz, 6 kV/mm, (150 V/mil) and load cycled daily to 90°C conductor, with water inside the pipe and outside of the samples, for periods of up to 3 years. DC testing was performed before and during the aging. An anticipated significant reduction in the AC breakdown strength is observed in control cables (not DC tested), from 44 kV/mm (1100 V/mil) for unaged cables, to 10 kV/mm (250 V/mil), for aged cables. However, there was no further reduction in the AC breakdown strength of cables subjected to DC testing as compared to those that are not tested with DC. It is concluded that AC breakdown strength is not an effective diagnostic tool for determining the effect of DC testing of URD cables aged under the conditions described |
| |
Keywords: | |
|
|