首页 | 本学科首页   官方微博 | 高级检索  
     

交流特高压输电线路绝缘子串污秽耐压特性试验
引用本文:徐涛,吴光亚,周文俊.交流特高压输电线路绝缘子串污秽耐压特性试验[J].高电压技术,2007,33(7):9-13.
作者姓名:徐涛  吴光亚  周文俊
作者单位:武汉大学电气工程学院,武汉430072;国网武汉高压研究院,武汉430074;国网武汉高压研究院,武汉430074;武汉大学电气工程学院,武汉430072
基金项目:国家电网公司特高压交流输电关键技术研究项目
摘    要:为研究1000kV特高压输电线路绝缘子串的污耐压特性,按照真型布置,依据GB/T4585-2004采用升降法求取了其50%污秽闪络电压。研究内容包括绝缘子串长与50%人工污秽耐受电压U50%的关系,不同串型下的污耐压特性,附灰密度(NSDD)、上下表面不均匀积污对污耐压的影响等。试验表明,绝缘子串长与U50%呈非线性趋势,按照线性拟合求取的U50%较试验所得出的结果高1.6~10.2%;NSDD的增加使绝缘子的U50%下降;上下表面不均匀积污比均匀积污时的U50%高等。研究结果可供1000kV交流特高压工程绝缘子串的选型及污秽外绝缘配置参数。

关 键 词:1000kV  交流输电线路  绝缘子串  污秽耐压  附灰密度  非线性
文章编号:1003-6520(2007)07-0009-05
修稿时间:2007-05-10

Flashover Voltage Characteristic of 1000kV AC Transmission Line Insulator Strings Under Polluted Conditions
XU Tao,WU Guang-ya,ZHOU Wen-jun.Flashover Voltage Characteristic of 1000kV AC Transmission Line Insulator Strings Under Polluted Conditions[J].High Voltage Engineering,2007,33(7):9-13.
Authors:XU Tao  WU Guang-ya  ZHOU Wen-jun
Affiliation:1. School of Electrical Engineering, Wuhan University, Wuhan 430072, China; 2. Wuhan High Voltage Research Institute of SGCC, Wuhan 430074, China
Abstract:This paper researched the artificial pollution withstand voltage character of 1000kV AC overhead line insulator strings in real layout.Using up and down lest methods,the 50% flashover voltage of insulator strings under polluted condition have been obtained according to GB/T 4585-2004.The relation between 50% artificial pollution power withstand voltage U50% with the length of insulator string,the character of artificial pollution withstand voltage in different string types,the impact of NSDD and non-uniform pollution of up and down surface to artificial pollution withstand voltage have been researched.The paper get that the relation of U50% and the length of insulator strings is nonlinear,U50% of linear fitting is 1.6% to 20% higher than that of test;if pollution external design is proceeded according to linear relation,the pieces of insulator strings will be 1.6% to 10.2% less than that by test.U50% of insulator will be decreased with the increment of NSDD,U50% of insulator is higher in non-uniform pollution condition than uniform pollution condition.The achievement of this paper are very important to choose and design insulator strings of 1000kV AC transmission line.
Keywords:1000kV  AC transmission line  insulator string  pollution withstand voltage  NSDD  non-linear
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号