首页 | 本学科首页   官方微博 | 高级检索  
     

烯烃厂6kV变电所无功补偿改造
引用本文:董永强.烯烃厂6kV变电所无功补偿改造[J].齐鲁石油化工,2013(1):29-31,39.
作者姓名:董永强
作者单位:中国石化齐鲁分公司烯烃厂
摘    要:针对烯烃厂6 kV变电所电功率因数存在的不足,利用调压式无功补偿原理,对并联电容器补偿容量进行了计算,并采取了谐波抑制措施。工业运行结果表明:采用并联电力电容器后,按照现负荷35 MW,其功率因数由0.8补偿到0.9,可降低上级主变有功损耗达0.9 M。

关 键 词:功率因数  无功补偿  电力电容器  谐波  降低损耗

REACTIVE-LOAD COMPENSATION REVAMP ON 6 kV POWER SUBSTATION OF THE OLEFIN COMPLEX
Dong Yongqiang.REACTIVE-LOAD COMPENSATION REVAMP ON 6 kV POWER SUBSTATION OF THE OLEFIN COMPLEX[J].Qilu Petrochemical Technology,2013(1):29-31,39.
Authors:Dong Yongqiang
Affiliation:Dong Yongqiang(Olefin Plant of Qilu Branch Co.,SINOPEC,Zibo Shandong 255400)
Abstract:Aimed at deficiency existing in electricity power tactor ot the O k V power suostation in Olefin Complex, calculated compensation capacity of the parallel capacitor adopting pressure adjustment type reactive - load compensation principle, and used harmonic wave suppression measures. Industrial running results showed that based on present load of 35 MW, power factor of the power substation was compensated from 0. 8 to 0. 9, and active power loss of the su- perior main transformer was decreased by 0. 9 MW after application of the parallel power capacitor.
Keywords:power factor  reactive - load compensation  power capacitor  harmonic wave  loss reduction
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号