调谐方式对消弧线圈并联运行的影响
引用本文:朱少林,谢聿琳,叶力行. 调谐方式对消弧线圈并联运行的影响[J]. 电力系统及其自动化学报, 2006, 18(1): 82-85
作者姓名:朱少林  谢聿琳  叶力行
作者单位:福州电业局,福州,350001;福州电业局,福州,350001;福州电业局,福州,350001
摘    要:随着自动补偿消弧线圈的广泛应用,自动补偿装置的并联运行成为影响配电网安全运行的关键问题之一。本文通过分析消弧线圈并联运行的工作原理和地区配电网的实测数据,讨论了“预调式”和“随调式”自动补偿消弧线圈可能出现的并联运行情况,提出了并联运行需注意的问题及建议的运行方式。优先考虑不同调谐方式的装置并联运行,对已采用预调式消弧线圈的母线并联运行应选择同型号的补偿装置,避免随调式消弧线圈装置的并联运行,并在控制条件允许时,适当采用手动调节方式以改善并联运行方式的灵活性。

关 键 词:配电网  并联运行  调谐方式  消弧线圈
文章编号:1003-8930(2006)01-0082-04
收稿时间:2005-03-02
修稿时间:2005-04-25

Effect of Automatic Tuning Mode Principle on Parallel Operation of Arc-Suppression Coil
ZHU Shao-lin,XIE Yu-lin,YE Li-xing. Effect of Automatic Tuning Mode Principle on Parallel Operation of Arc-Suppression Coil[J]. Proceedings of the CSU-EPSA, 2006, 18(1): 82-85
Authors:ZHU Shao-lin  XIE Yu-lin  YE Li-xing
Affiliation:Fuzhou Electric Power Bureau, Fuzhou 350001, China
Abstract:With the extensive application of automatic tuning arc-suppression coil,the secure operation of distribution network influenced by the parallel operation of automatic tuning device becomes one of the key problems.By analyzing the principle and the field data of distribution network,the instances of parallel operation under different automatic tuning modes are discussed.The potential problems concerned in parallel operation and the propositional operation modes are presented in this paper.The parallel operation with different automatic tuning devices is recommended as the preferential option.The homotypic device is suggested to be used for the parallel operation with arc-suppression coil under preadjustment mode and the parallel operation with arc-suppression coil under instantaneous adjustment mode is not preferred.The manual mode is suggested to be properly used under certain control conditions to improve the flexibility.
Keywords:distribution network  parallel operation  tuning mode  arc-suppression coil