摘    要:蓄电池企业电池化成设备的大量应用,产生的高次电流谐波严重污染了供电电网,使供电变压器严重发热,电容器及电力电缆等设备的运行损耗增加。针对电流谐波给电网带来的危害,结合某蓄电池企业的实际工况,采用多路单调谐滤波器对供电电网的电流谐波实施综合治理,既消除了谐波对电网的污染,又提高了功率因数。介绍了多路单调谐滤波治理的基本原理、综合治理措施及结果。

关 键 词:化成设备  多路单调谐滤波器  谐波治理  无功补偿

Study on Harmonic Treatment Program in Battery Plants
LIAO Yuwu. Study on Harmonic Treatment Program in Battery Plants[J]. Power Supply Technologles and Applications, 2009, 12(5): 16-19
Authors:LIAO Yuwu
Affiliation:LIAO Yuwu (Physics&Electronics Information Technology Department,Xiangfan University,Xiangfan 441053,China)
Abstract:Because of the wide application of battery chemical facilities in battery plants,the induced highorder harmonic currents have seriously polluted electricity network.So the power transformers suffer some problems,such as severe overheating,increasing operation loss in capacitors,power cables and other equipment. Considering the dangers of harmonic currents to the grid and actual conditions of a battery plant,the multiplex single-tuned filter is adopted to reduce the harm of harmonic currents.This method can ...