Operational experience with a 10 MW diesel driven heat pump at Frederikshavn, Denmark |
| |
Authors: | O. Fan e, Manager |
| |
Affiliation: | Heat Pump department, Burmeister and Wain Scandinavian Contractor A/S, PO Box 51-DX 1002 Copenhagen K, Denmark |
| |
Abstract: | Test results from a 10 month running-in and operation period are presented for a 10 MW diesel driven compression type heat pump. The heat pump was delivered by Burmeister and Wain, Scandinavian Contractor A/S to the Municipality of Frederikhavn in Denmark. The COP is between 1.81 and 1.87 with an evaporation temperature at 2°C and a temperature of 85°C on the outgoing water at full load. |
| |
Keywords: | |
本文献已被 ScienceDirect 等数据库收录! |
|