首页 | 本学科首页   官方微博 | 高级检索  
     

35kV系统谐振过电压事故分析
引用本文:龚俊祥,张 菁. 35kV系统谐振过电压事故分析[J]. 山东电力技术, 2016, 43(2): 66-68
作者姓名:龚俊祥  张 菁
作者单位:1.国网山东省电力公司威海供电公司
摘    要:分析一起35 k V系统谐振过电压事故产生的原因。通过系统等效电路图计算系统中性点电压及三相对地电压幅值,利用电压向量图表达系统中性点及三相对地电压随系统角差的变化趋势。经分析,事故根本原因为:系统间某联络开关非全相形成串联线性谐振回路,产生谐振过电压。提出了防止谐振过电压的产生和降低其影响的措施。

关 键 词:35  k  V系统  谐振  过电压

Analysis of Resonance Overvoltage Accident in 35 kV Power System
GONG Junxiang and ZHANG Jing. Analysis of Resonance Overvoltage Accident in 35 kV Power System[J]. Shandong Electric Power, 2016, 43(2): 66-68
Authors:GONG Junxiang and ZHANG Jing
Affiliation:State Grid Weihai Power Supply Company and State Grid Weihai Power Supply Company
Abstract:The cause of one resonance overvoltage accident is analyzed. Voltages of three phases and the neutral point are calculated using the equivalent circuit of power system. Voltage change trends of three phases and the neutral point with the system angle difference are showed by voltage vector diagrams. Conclusion is reached that the root cause of the accident is the resonance overvoltage of the series-wound linear resonance circuit caused by the open-phase operation of interconnecting switch. Corresponding measures are put forward for the prevention of the resonance overvoltage.
Keywords:
本文献已被 CNKI 维普 等数据库收录!