Interruption capability of CF/sub 3/I Gas as a substitution candidate for SF/sub 6/ gas
Authors:Taki   M. Maekawa   D. Odaka   H. Mizoguchi   H. Yanabu   S.
Affiliation:Tokyo Denki Univ.;
Abstract:We studied the interruption performance of CF3I gas because its environmental effect is smaller than that of SF6 gas with a model arc-extinguishing chamber. First, we measured the arc time constant and arc power loss coefficient using Mayr's equation. Comparing CF3I with other gases, the arc time constants are SF63I2< H22. The arc power loss coefficient is H2>SF6 >CO2>Air>N2 >CF3I. Next, we evaluated the short line fault (SLF) interruption capability by measuring the di/dt-dv/dt characteristic. Consequently, the SLF interruption performance of pure CF3I was about 0.9 times that of SF6. However, CF3I application to gas insulated switchgear (GIS) and gas circuit breakers (GCB) is difficult because the liquefying temperature of the gas is high. Therefore, we adopted a countermeasure to obtain a lower liquefying temperature mixing CF3I with CO2. The result showed that the SLF interruption performance of the mixture approximated that of pure CF3I when the ratio of CF3 I exceeds 20%