首页 | 本学科首页   官方微博 | 高级检索  
     

一起线路故障引起主变中性点间隙击穿的原因分析
引用本文:张强,吴绍武,王德全.一起线路故障引起主变中性点间隙击穿的原因分析[J].电气技术,2016(11):153-156.
作者姓名:张强  吴绍武  王德全
作者单位:江苏省电力公司淮安供电公司,江苏淮安,223002
摘    要:某变电站110k V进线线路发生单相接地故障时,引起该变电站不接地主变中性点间隙零序保护动作切除运行中主变。通过现场检查及故障录波图,对线路故障而主变保护动作的原因进行了分析,并提出了针对性的建议,以保证系统设备的安全运行。

关 键 词:继电保护  单相接地  间隙零序  间隙击穿

Cause Analysis of Transformer Neutral Point Gap Breakdown Caused by Line Fault
Abstract:The transmission line of a substation occur a 110kV single phase grounding fault which causes the action of the main transformer neutral point gap zero sequence protection and the cutting of main transformer operation. Through inspection of fault place and recorded fault data, the paper analyses the cause of the action of the main transformer protection caused by line fault, and gives some specific recommendations in order to ensure the safe operation of the system equipment.
Keywords:relay protection  single phase grounding fault  gap zero-sequence  gap breakdown
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号