基于FBG的电力杆塔倾角传感器研究
引用本文:杨洪磊,梁仕斌,李川,苗雪鹏,昌明.基于FBG的电力杆塔倾角传感器研究[J].传感器与微系统,2013(11):21-24.
作者姓名:杨洪磊  梁仕斌  李川  苗雪鹏  昌明
作者单位:[1]昆明理工大学云南电网公司研究生工作站,云南昆明650217 [2]云南电力试验研究院集团有限公司电力研究院,云南昆明650217 [3]昆明理工大学信息工程与自动化学院,云南昆明650500 [4]河南科信电缆有限公司,河南周口466000 [5]昆明能讯科技有限责任公司,云南昆明650217
基金项目:云南省应用基础研究计划资助项目(2013FZ021)
摘    要:电力杆塔监测对保证输电线路运行安全具有重要意义。对基于光纤Bragg光栅(FBG)的电力杆塔倾角传感器进行研究,底端固定于传感器外壳上的等强度悬臂梁自由端挂有重物,且在等强度悬臂梁两侧对称中心线上各粘贴一个FBG。电力杆塔发生倾斜时,重物带动等强度悬臂梁自由端产生挠度,使FBG产生中心波长移位,对中心波长进行监测即可实现杆塔倾斜角度测量。实验表明:测量小角度(小于15°)时,重复性误差为l%Fs,非线性误差为0.4%FS,滞后误差为0.8%FS;测量大角度(15°-45°)时,重复性误差为1.5%FS,非线性误差为0.77%FS,滞后误差为1.1%FS。

关 键 词:光纤Bragg光栅  倾角  等强度悬臂梁  重物  电力杆塔

Research of electric power tower tilt angle sensor based on FBG
YANG Hong-lei,LIANG Shi-bin,LI Chuan,MIAO Xue-peng,CHANG Ming.Research of electric power tower tilt angle sensor based on FBG[J].Transducer and Microsystem Technology,2013(11):21-24.
Authors:YANG Hong-lei  LIANG Shi-bin  LI Chuan  MIAO Xue-peng  CHANG Ming
Affiliation:1. Graduate Workstation of Kunming University of Science and Technology &Yunnan Power Grid Corporation, Kunming 650217, China; 2. Yunnan Electric Power Test & Research Group Co Ltd ,Electric Power Research Institute, Kunming 650217, China; 3. School of Information Engineering and Automation, Kunming University of Science and Technology, Kunming 650500, China; 4. Henan Kosen Cable Co Ltd, Henan 466000, China; 5. Kunming ENERSUN Technology Co Ltd,Kunming 650217 ,China)
Abstract:Electric power towers monitoring is of great significance to ensure transmission lines operate safely. A tilt sensor based on fiber Bragg grating(FBG) for electric power tower monitoring is researched, heavy weights are fasten on the free end of equal strength cantilever beam, of which the bottom is fixed on the sensor shell, two FBGs are pasted on the center symmetrical lines on both sides of equal strength cantilever beam, heavy weights generates deflection on the free end of the equal strength cantilever beam when the electric power tower is slanting,leading to shift of center wavelengths FBG angle of the electric power tower can be measured by monitoring center wavelengths of FBG in the sensor. Experiment indicates that the repeatability error is 1% FS, the nonlinear error is 0.4 % FS, the hysteresis error is 0.8 % FS ,when the tilt angle is less than 15°. The repeatability error is 1.5%FS,the nonlinear error is 0.77 % FS,the hysteresis error is 1.1% FS,when the tilt angle range of 15°-45°
Keywords:fiber Bragg grating(FBG)  tilt angle  equal strength cantilever beam  heavy weight  electric powertower