再生水回用于工业循环冷却水系统的污垢分析与研究
引用本文:岳冠华,邹红云,尚丽民,许萍.再生水回用于工业循环冷却水系统的污垢分析与研究[J].给水排水,2012,38(2):49-53.
作者姓名:岳冠华  邹红云  尚丽民  许萍
作者单位:1. 北京建筑工程学院城市雨水系统与水环境省部共建教育部重点实验室,北京,100044
2. 北京建筑工程学院环境与能源工程学院,北京,100044
基金项目:国家水体污染控制与治理科技重大专项
摘    要:以北京京能热电厂循环冷却系统的再生水补水为试验用水,进行了静态结垢、动态污垢监测及动态模拟试验.结垢产物的XRD分析结果表明,再生水在溶液中和不同材质加热棒上的结垢产物主要是含镁方解石;黄铜换热管内的主要结垢产物是含镁方解石、石英;不锈钢换热管内的主要结垢产物是含镁方解石、石英和磁铁矿.通过XRF分析仪,对各种试验条件下的污垢进行元素全分析,并对各种污垢产生的原因和规律做了分析.

关 键 词:热电厂  再生水  循环冷却水系统  污垢

Study on the fouling in the industrial recycling cooling system with reclaimed wastewater
Yue Guanhua , Zou Hongyun , Shang Limin , Xu Ping.Study on the fouling in the industrial recycling cooling system with reclaimed wastewater[J].Water & Wastewater Engineering,2012,38(2):49-53.
Authors:Yue Guanhua  Zou Hongyun  Shang Limin  Xu Ping
Affiliation:1(1.Key Laboratory of Urban Stormwater System and Water Environment of the Education Ministry, Beijing University of Civil Engineering and Architecture,Beijing 100044,China; 2.School of Environment and Energy Engineering,Beijing University of Civil Engineering and Architecture,Beijing 100044,China)
Abstract:In this paper,the water samples were taken from the recycling cooling system of Beijing Jingneng Thermoelectric Plant.The static scaling,dynamic fouling monitor and dynamic simulation tests were performed.The XRD results of fouling indicated that the scaling of reclaimed wastewater in solution and on different material heating bar was mainly composed of calcite;the fouling in brass heat exchange tube mainly of calcite and quartz;in stainless steel heat exchange tube mainly of calcite,quartz and magnetite.The element analysis of fouling forming under all kinds of test condition was performed by XRF and the forming reasons and principles of different fouling were also investigated.
Keywords:Thermoelectric plant  Reclaimed wastewater  Recycling cooling system  Fouling
本文献已被 CNKI 万方数据 等数据库收录!