Abstract: | In this paper, we proposed a method to predict the capacity of a heat exchanger by considering static pressure distributions of refrigerants. The thermal network method was modified by adding an equivalent heat generation term into a heat balance equation that was connected with calculated 1D static pressure distributions of refrigerants. An experiment was performed with a heat exchanger having two rows and two passes to verify the accuracy of the proposed method. The result showed the error of the predicted capacity to be less than 1% for an evaporator and less than 2% for a condenser. © 2002 Wiley Periodicals, Inc. Heat Trans Asian Res, 31(5): 376–390, 2002; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/htj.10039 |