Performance evaluation of heat exchanger using alternative refrigerant R407C
Authors:Masayuki Nonaka  Hiroaki Matsushima  Kazuhiro Endoh  Kazuya Matsuo  Kazuo Fujibayashi
Abstract:R22 (HCFC22) has been widely used as the refrigerant in air conditioners. According to the Montreal protocol for ozone layer protection, the total production of HCFCs has been capped since the beginning of 1996. Zeotropic refrigerant mixture R407C and nearly azeotropic refrigerant mixture R410A have been selected as alternatives to R22. We examined refrigerant passages in heat exchangers used in heat pump‐type room air conditioners using zeotropic refrigerant R407C through simulation, and obtained the following conclusions. In an indoor heat exchanger, a counter flow configuration when operating as a condenser has higher temperature efficiency. When an outdoor heat exchanger operates as an evaporator, a configuration that suppresses the temperature glide by partially reducing the refrigerant passage not only produces high efficiency, but also reduces the frost formation on fins. © 2002 Wiley Periodicals, Inc. Heat Trans Asian Res, 31(8): 626–638, 2002; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/htj.10064
Keywords:heat exchanger  air conditioning  refrigerant  zeotropic refrigerant mixture  heat exchanger simulator  R407C