避雷器阻性电流测试新方法
引用本文:张伟平. 避雷器阻性电流测试新方法[J]. 电瓷避雷器, 2011, 0(6): 112-116
作者姓名:张伟平
作者单位:广东电网公司东莞供电局,广东东莞,523000
摘    要:供电可靠性的要求使设备试验由原来的停电预试为主转为带电测试为主的模式,带电测试工作得到加强.在进行避雷器带电测试的过程中,由于受避雷器的安装排列方式等的影响,经常出现阻性电流负值,三相阻性电流值相差很大的情况,导致判断困难.笔者通过大量的现场测试经验,总结了一套测量氧化锌避雷器阻性电流的新方法——实际相角法,该方法使运...

关 键 词:避雷器  阻性电流  实际相角法

New Testing Methods for Arrester Resistive Current
ZHANG Wei-ping. New Testing Methods for Arrester Resistive Current[J]. Insulators and Surge Arresters, 2011, 0(6): 112-116
Authors:ZHANG Wei-ping
Affiliation:ZHANG Wei-ping(Dongguan Power Supply Bureau of Guangdong Power Grid Corporation,Dongguan 523000,China)
Abstract:For the requirement of reliability of power supply,the equipment test is changed from power outages at the request of preventive test to a live test mode;hence the live test has been strengthened.During the live testing process for arrester,the resistive current is frequently negative and the three-phase resistive current values vary greatly due to the installation arrangement of surge arresters,which can result in judgment difficult.A new testing method is summarized: the actual phase angle method for resistive current of MOA through a lot of field testing experience.The method enables measurement of arrester resistive current in operation unaffected by the installation arrangement of surge arrester and enables to use resistive current directly for judging deterioration of arrester which is more direct and accurate.
Keywords:arrester  resistive current  the actual phase angle method