首页 | 本学科首页   官方微博 | 高级检索  
     

PEMO2000接地极线监测特性分析
引用本文:王磊.PEMO2000接地极线监测特性分析[J].电力建设,2008,29(8):41-0.
作者姓名:王磊
作者单位:( 中国南方电网超高压输电公司天生桥局, 贵州省兴义市, 562400)
摘    要:南网超高压公司的几个换流站采用PEMO2000 装置来监测接地极线故障。通过对PEMO2000 监测特性的分析, 可知PEMO2000 可以准确监测接地极线上的永久性单线金属接地、线间短路和接地极线开路故障, 但是无法监测到故障时间小于2 s 和高阻抗接地故障。PEMO2000 的测量与线路行波测距中的利用重合闸信号测距方法接近, 国内厂家可以考虑借用双端测距的方法实现接地极线的实时检测。

关 键 词:PEMO2000  换流站  接地极线  监测特性  
收稿时间:2010-01-25
修稿时间:2010-01-25

Analysis of Ground Wire Monitoring Characteristics of PEMO2000
WANG Lei.Analysis of Ground Wire Monitoring Characteristics of PEMO2000[J].Electric Power Construction,2008,29(8):41-0.
Authors:WANG Lei
Abstract:PEMO2000 is used to ground wire fault monitoring by several converter stations of UHV Transmission Co., of China Southern Power Grid. Through analysis of its monitoring characteristics, it known that PEMO2000 can correctly monitoring faults, including permanent single metal-wire grounding, short circuit between lines, and ground wire open circuit. However, it is unable to identify faults with duration less than 2 seconds and high-impedance ground faults. Because the principle of PEMO2000 is similar to the method used in line traveling wave range finding, domestic manufacturers can realize real-time ground wire monitoring through range finding from both ends.
Keywords:PEMO2000
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力建设》浏览原始摘要信息
点击此处可从《电力建设》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号