首页 | 本学科首页   官方微博 | 高级检索  
     

注入式定子接地保护在金安桥600MW机组上的应用
引用本文:赵林,胥亚宁. 注入式定子接地保护在金安桥600MW机组上的应用[J]. 水力发电, 2011, 37(1)
作者姓名:赵林  胥亚宁
作者单位:金安桥水力发电厂,云南丽江,674100
摘    要:阐述了大容量发电机定子接地保护的要求,描述了金安桥水力发电厂20 Hz电源注入式定子接地保护原理的构成,并详细介绍了注入式保护与传统的双频式定子接地保护相比较的优势;结合金安桥水电站的实际运行说明中性点接地变压器变比大小、接地变二次电阻值与定子单相接地保护灵敏度的相互配合的意义.

关 键 词:20 Hz电源  注入式  接地电流  配电变压器  定子接地保护

Application of Injected-type Stator Ground Protection on the 600 MW Unit of Jin'anqiao Hydropower Station
Zhao Lin,Xu Yaning. Application of Injected-type Stator Ground Protection on the 600 MW Unit of Jin'anqiao Hydropower Station[J]. Water Power, 2011, 37(1)
Authors:Zhao Lin  Xu Yaning
Affiliation:Zhao Lin,Xu Yaning(Jin'anqiao Hydropower Plant,Lijiang 674100,Yunnan,China)
Abstract:The stator ground protection based on injecting 20 Hz power source signal for Jin'anqiao Hydropower Station was introduced,and the injected-type and traditional dual-frequency protections were compared.The actual operation of Jin'anqiao Hydropower Station shows that the matches between the ratio of neutral transformer,the ground resistance and the sensitivity of stator single-phase ground protection are important for stator ground protection.
Keywords:20 Hz power source  injected-type  grounding current  distribution transformer  stator ground protection  
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号