Condensation heat transfer and pressure drop of R134a in annular helicoidal pipe at different orientations
Affiliation:1. School of Nuclear Engineering, Purdue University West Lafayette, IN 47907, USA;2. Institute of Nuclear Engineering and Science, National Tsing Hua University, Hsinchu 30013, Taiwan;3. Division of Energy and Environmental Systems, Graduate School of Engineering, Hokkaido University, 060-8628 Spapporo, Japan;4. R&D Center, Tokyo Electric Power Company, 230-8510 Yokohama, Japan
Abstract:Experimental investigations were conducted to determine the condensation heat transfer and pressure drop of refrigerant R134a in annular helicoidal pipe at three inclination angles. The experiments were performed with the Reynolds number of R134a ranging from 60 to 200, and that of cooling water from 3600 to 22 000; temperatures of R134a at 30 °C and 35 °C, and cooling water at 16 °C, 20 °C and 24 °C. The experimental results indicated that the refrigerant Nusselt number was larger at lower refrigerant saturation temperature, and would increase with the increase of mass flow rates of refrigerant and cooling water. It was found that the refrigerant heat transfer coefficient of annular helicoidal pipe could be two times larger than that of equivalent plain straight pipe when the refrigerant Reynolds number was larger than 140. Comparison with identical helicoidal pipe with opposite flow channel arrangement revealed that the refrigerant heat transfer rate was larger when the refrigerant was flowing in the annular section at the cooling water Reynolds number larger than 4000, but the pressure drop was always larger in this flow channel arrangement.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号