首页 | 本学科首页   官方微博 | 高级检索  
     


The substitution of R134a with R744: An exergetic analysis based on experimental data
Authors:Ciro Aprea  Adriana Greco  Angelo Maiorino
Affiliation:1. Dipartimento di Ingegneria Industriale, Università di Salerno, via Ponte Don Melillo, 84084 Fisciano, Salerno, Italy;2. DETEC, Università degli Studi di Napoli Federico II, P.le Tecchio 80, 80125 Napoli, Italy
Abstract:This paper deals with the problem of R314a substitution with a natural refrigerant fluid. A comparison is performed between R134a and R744 (CO2). R134a is a hydrofluorocarbon with a large direct warming impact (GWP), whereas the R744 contribution is negligible. A comparative exergetic analysis, carried out with experimental tests, has been presented. This paper compares a commercial R134a refrigeration plant and a prototype R744 system working in a trans-critical cycle. Based on the experimental data an exergetic analysis has been carried out on the overall plant and on each device. The overall exergetic performances of the classical vapour compression plant working with R134a are consistently better than that of R744 (from a minimum of 20 to a maximum of 44%). The performance of the individual components of the plant has been analyzed, in order to pinpoint those contributing most to the decrease in the exergetic performance of R744.
Keywords:R134a  Transcritical cycle  Exergetic analysis  Exergy loss  Dioxyde de carbone  R134a  Cycle transcritique  Analyse exergétique  Perte d'exergie
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号