首页 | 本学科首页   官方微博 | 高级检索  
     


Modeling of a novel spool compressor with multiple vapor refrigerant injection ports
Authors:Margaret M Mathison  James E Braun  Eckhard A Groll
Affiliation:1. Marquette University, Department of Mechanical Engineering, 1637 W. Wisconsin Avenue, Milwaukee, WI 53233, USA;2. Purdue University, School of Mechanical Engineering, 140 S. Martin Jischke Drive, West Lafayette, IN 47907, USA
Abstract:A model of a novel rotary spool compressor has been developed to explore the effect of multiple injection ports on compressor and cycle performance. The thermodynamic model includes the effects of heat transfer and leakage and is numerically solved to predict the compressor power consumption and mass flow rate. Saturated vapor injection is modeled assuming that the injection pressures and the timing of the injection process can be controlled.The model predicts that adding a single injection port will provide a 12% increase in the cycle coefficient of performance (COP) when the compressor runs at 1907 rpm with R-22 evaporating at ?7 °C, condensing at 49 °C, and 15 °C of superheat. Adding a second, non-optimized injection port increases the COP by 16% compared to the cycle without injection. The model is used to investigate the effect of injection pressure, port location, and port diameter on cycle performance.
Keywords:Spool compressor  Novel compressor  Compressor modeling  Injection  Economizing  Air conditioning units  compresseur à rotor  compresseur innovant  modélisation des compresseurs  injection  économie  systèmes de conditionnement d'air
本文献已被 ScienceDirect 等数据库收录!